SMA SUNNY TRIPOWER CORE1-US Instrucciones De Instalación página 49

Ocultar thumbs Ver también para SUNNY TRIPOWER CORE1-US:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SMA Solar Technology America LLC
Name
Voltage monitoring of upper maximum threshold as
RMS value
Voltage monitoring median maximum threshold
(Overvoltage/Fast)
Voltage monitoring lower maximum threshold
(Overvoltage/Slow)
Voltage monitoring upper minimum threshold (Un-
dervoltage/Slow)
Voltage monitoring of median minimum threshold
(Undervoltage/Fast)
Voltage monitoring of lower minimum threshold as
RMS value
Voltage monitoring of upper max. thresh. as RMS
value for tripping time
Voltage monitoring median max. threshold trip.time
(Overvoltage/Fast, maximum time)
Voltage monitoring lower max. threshold trip. time
(Overvoltage/Slow, maximum time)
Voltage monitoring upper min. threshold trip. time
(Undervoltage/Slow, maximum time)
Voltage monitoring median min. threshold trip.time
(Undervoltage/Fast, maximum time)
Voltage monitoring of lower min.threshold as RMS
value for tripping time
Frequency monitoring upper minimum threshold
(Underfrequency)
Frequency monitoring lower maximum threshold
(Overfrequency)
Frq. monitoring upper min. threshold trip. time (Un-
derfrequency, maximum time)
Frq. monitoring lower max. threshold trip. time
(Overfrequency, maximum time)
Installation Manual
7 Commissioning
Value/range
Default value
220 V to 332.4 V
220 V to 332.4 V
220 V to 305 V
103.5 V to 277.0 V
103.5 V to 277.0 V
103.5 V to 277 V
0.05 s to 59 s
0.05 s to 59 s
0.1 s to 60 s
0.1 s to 60 s
0.1 s to 60 s
0.1 s to 60 s
44 Hz to 60 Hz
50 Hz to 65 Hz
0.1 s to 300 s
0.1 s to 300 s
STP50-US-40-IA-en_es-11
332.4 V
332.4 V
304.7 V
243.8 V
138.5 V
138.5 V
0.16 s
0.16 s
1.0 s
2.0 s
0.16 s
0.16 s
59.3 Hz
60.5 Hz
0.16 s
0.16 s
49