Maintenance; Notes On Safety For The Maintenance; Maintenance Programme; Checking And Cleaning - Riello RL 800/M TC FS2 Instrucciones De Uso

Quemadore de gasóleo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7

Maintenance

7.1

Notes on safety for the maintenance

The periodic maintenance is essential for the good operation,
safety, yield and duration of the burner.
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time.
The maintenance interventions and the calibration
of the burner must only be carried out by qualified,
authorised personnel, in accordance with the con-
tents of this manual and in compliance with the
DANGER
standards and regulations of current laws.
7.2

Maintenance programme

7.2.1

Checking and cleaning

Combustion
The optimum calibration of the burner requires an analysis of the
flue gases.
Significant differences with respect to the previous measure-
ments indicate the points where more care should be exercised
during maintenance.
Combustion head
Open the burner and make sure that all components of the
combustion head are in good condition, not deformed by the
high temperatures, free of impurities from the surroundings
and correctly positioned.
Current to the UV photocell (Fig. 33)
Clean the glass cover from any dust that may have accumulated.
Photocell is held in position by a pressure fit and can therefore be
removed by pulling it outward forcefully.
Min value for a good work: 70 μA.
If the value is lower, it can depend on:
exhausted photocell
ow current (lower than 187 V)
bad regulation of the burner.
In order to measure the current, use a microammeter of 100 A
c.c., connected to the photocell, as in the scheme, with a capac-
itor of 100 F - 1V c.c. at the same level of the instrument.
D1143
Burner
Check for excess wear or loose screws, especially on cams 3)
(Fig. 27).
Clean the outside of the burner.
Clean and grease the cam variable profile.
Fan
Check to make sure that no dust has accumulated inside the fan
or on its blades, as this condition will cause a reduction in the air
flow rate and provoke polluting combustion.
20034064
Maintenance
Before carrying out any maintenance, cleaning or checking oper-
ations:
disconnect the electricity supply from the burner
by means of the main switch of the system;
DANGER
close the fuel interception tap.
DANGER
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.
Filters (Fig. 34)
Check the filtering baskets on line 1) and at nozzle 2) present in
the system.
Clean or replace if necessary.
If rust or other impurities are observed inside the pump, use a
separate pump to lift any water and other impurities that may
have deposited on the bottom of the tank.
Fig. 33
Pump
Delivery pressure must correspond with the table on page 16.
The depression must be less than 0.45 bar.
Unusual noise must not be evident during pump operation.
If the pressure is found to be unstable or if the pump runs noisily,
the flexible hose must be detached from the line filter and the fuel
must be sucked from a tank located near the burner. This meas-
ure permits the cause of the anomaly to be traced to either the
suction line or the pump.
If the problem lies in the suction line, check to make sure that the
filter is clean and that air is not entering the piping.
28
GB
LIGHT OIL OPERATION
D2012
Fig. 34

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido