Annex C: Table FOR SERVICEMAN
Code
Description
1. DHW MODE SETTING
1.1
DHW MODE
The selection of whether DHW mode is avalaible
Temperature difference between T5 (actual temp. of DHW) and
1.1.1
dT5_ON
T5S (target temp. of DHW) for turn the unit ON (T5 ” T5S - dT5_ON)
1.1.2
dT1S5
The correct value for T1S (target outlet water temp.)
1.1.3
T4DHWMAX
The maximum operating ambient temp.
1.1.4
T4DHWMIN
The minimum operating ambient temp.
1.1.5
t_INTERVAL DHW
The compressor start time interval
1.2
TANK HEATER
The selection of whether TANK HEATER is avalaible
Temp. difference between T5 and T5S that turn the tank heater OFF
1.2.1
dT5_TBH_OFF
(T5 • T5S + dT5_TBH_OFF)
The temp. only when the ambient temperature lower than it the
1.2.2
T4_TBH_ON
tank heater will operate
1.2.3
t_TBH_DELAY
The time that the compressor has run before starting the tank heater
1.3
DISINFECT
The selection of whether DISINFECT mode is avalaible
1.3.1
T5S_DI
The setting temp. of water in the domestic water tank
1.3.2
t_DI_HIGHTEMP.
The time high temp. of water to be lasted
1.3.3
t_DI_MAX
The time that desinfection to be lasted
1.4
DHW PRIORITY
The selection of whether DHW priority is avalaible
1.4.1
t_DHWHP_MAX
The maximum operation time of heat pump
1.4.2
t_DHWHP_RESTRICT
The operation time for space heating/cooling operation
1.5
DHW PUMP
The selection for whether the DHW pump is installed or not
1.5.1
TIMER RUNNING
The selection for whether the DHW pump will run as timed
1.5.2
DISINFECT
The selection for whether the DHW pump will run as disinfect mode is on
PUMP RUNNING
1.5.3
The pump running time
TIME
2. COOL MODE SETTING
2.1
COOL MODE
The selection of whether space cool mode is avalaible
2.2
T1S RANGE
The range of target outlet water temp.
2.3
T4CMAX
The maximum operating ambient temp.
2.4
T4CMIN
The minimum operating ambient temp.
The temp. difference between T1 (actual outlet water temp.) and
2.5
dT1SC
T1S (target outlet water temp.) for starting the unit (T1 • T1S + dT1SC)
The temp. difference between Ta (actual room temp.) and
2.6
dTSC
TS (target room temp.) for starting the unit when room
thermostat is installed (T1 • T1S + dTSC)
2.7
t_INTERVAL_C
The compressor start time interval
3. HEAT MODE SETTING
3.1
HEAT MODE
The selection of whether space heat mode is avalaible
3.2
T1S RANGE
The range of target outlet water temp.
3.3
T4HMAX
The maximum operating ambient temp.
3.4
T4HMIN
The minimum operating ambient temp.
The temp. difference between T1 (actual outlet water temp.) and
3.5
dT1SH
T1S (target outlet water temp.) for starting the unit (T1 ” T1S - dT1SH)
The temp. difference between Ta (actual room temp.) and
3.6
dTSH
TS (target room temp.) for starting the unit when room
thermostat is installed (Ta ” TS - dTSH)
3.7
t_INTERVAL_h
The compressor start time interval
Value
(T1S = T5 + dT1S5)
176
Default value
Range
Step
YES
YES/NON
-
5
2 ~ 10
1
10
5 ~ 20
1
43
35 ~ 43
1
-10
-20 ~ 5
1
5
5 ~ 30
1
YES
YES/NON
-
5
2 ~ 10
1
5
-5 ~ 20
1
90
60 ~ 240
5
YES
YES/NON
-
65
60 ~ 70
1
15
5 ~ 45
5
210
90 ~ 300
5
YES
YES/NON
-
180
60 ~ 600
5
180
60 ~ 600
5
NON
YES/NON
-
YES
YES/NON
-
YES
YES/NON
-
5
5 ~ 120
1
YES
YES/NON
-
LOW
LOW/HIGH
-
43
35 ~ 46
1
10
-5 ~ 25
1
5
2 ~ 10
1
2
1 ~ 10
1
5
5 ~ 30
1
YES
YES/NON
-
LOW
LOW/HIGH
-
25
10 ~ 30
1
-15
-5 ~ 20
1
5
2 ~ 10
1
2
1 ~ 10
1
5
5 ~ 60
1
Unit
-
ºC
ºC
ºC
ºC
min
-
ºC
ºC
min
-
ºC
min
min
-
min
min
-
-
-
min
-
-
ºC
ºC
ºC
ºC
min
-
-
ºC
ºC
ºC
ºC
min