5 Installation
CAUTION
Result
5.5
58
Risk of injury due to damaged strain relief on the cables!
Connecting cables which are not strain-relieved may be damaged or
severed. This can result in serious personal injury or material damage.
Fit the cable strain relief on site.
|
Adequately secure connecting cables entering the device by a cable
|
strain relief (cable mounting rail).
Only use aluminium or plastic cable clips for strain relief on the cables.
|
Check all cable leads before connecting the cabling.
6. Secure the cables on cable mounting rails.
7. Secure the safety cover.
The grid is connected.
Connecting the auxiliary power supply
Materials required
Cable 1-phase, 230 V, 50 Hz
|
Prerequisites
Ensure that the auxiliary power supply cables are fully deenergised.
|
TN grid.
|
Series fuse 16 A, type B or similar available.
|
If there is no auxiliary power supply (230 V
|
galvanically isolated transformers with 2.5 kVA output to supply the
central inverter with 230 V.
Connecting the auxiliary power supply
Operating manual
), use separate
AC
Transformerless central inverter