INSTALLATION
Installation in premises with re hazards is forbidden. Installation in residential premises (except for sealed operation appliances)
is also forbidden:
in which there are liquid fuel-operated appliances with continuous or intermittent operation, which draw the combustion
air in the room in which they are installed, or
in which there are type B gas appliances intended for room heating, with or without production of domestic hot water and
in adjacent and adjoining premises, or
in which, in any case, the depression measured during installation between the internal and external environment is
greater than 4 Pa
Installations in bathrooms, bedrooms and studio ats
Installation in bathrooms, bedrooms and studio ats is only allowed for sealed or closed hearth appliances with ducted
combustion air taken from the outside.
Installation premises requirements
The support surfaces and/or points must have a suitable load-bearing capacity to support the weight of the appliance, of the
accessories and coatings.
The adjacent, side and rear walls and the supporting surface must be made of non-combustible material. Installation near combustible
materials or those sensitive to heat is permitted as long as there is a suitable safety distance, which for pellet stoves is equal to:
REFERENCES
A
B
C
B
gure 1
In any case the temperature of the adjacent combustible materials must not reach a temperature equal to or greater than the
room temperature increased by 65°C.
The minimum volume of the premises in which to install the appliance must be greater than 15 m³.
INSERTS INSTALLATION
In the event of installation of inserts, access to the internal parts of the device is to be prevented and, during extraction, it should
not be possible to access to live parts.
Any wiring, such as a power supply cable or room sensors must be positioned so as not to be damaged during movement of the
insert, or come into contact with hot parts.
INFLAMMABLE OBJECTS
Flue
C
Inspection
200 mm
1500 mm
200 mm
A
gure 2
ENGLISH
NON INFLAMMABLE OBJECTS
100 mm
750 mm
100 mm
Air inlet
S= oor protection
S
57