rature every 3 minutes.
The requested values and recording conditions
are set via a PC with PACTware/DTM or the
control system with EDD. Data are thus read out
and also reset.
Event memory
Up to 500 events are automatically stored with a
time stamp in the sensor (non-deletable). Each
entry contains date/time, event type, event de-
scription and value. Event types are for example:
•
Modification of a parameter
•
Switch-on and switch-off times
•
Status messages (according to NE 107)
•
Error messages (according to NE 107)
The data are read out via a PC with PACTware/
DTM or the control system with EDD.
Echo curve memory
The echo curves are stored with date and time
and the corresponding echo data. The memory
is divided into two sections:
Echo curve of the setup: This is used as
reference echo curve for the measurement
conditions during setup. Changes in the measu-
rement conditions during operation or buildup
on the sensor can thus be recognized. The echo
curve of the setup is stored via:
•
PC with PACTware/DTM
•
Control system with EDD
•
Display and adjustment module
Further echo curves: Up to 10 echo curves
can be stored in a ring buffer in this memory
section. Further echo curves are stored via:
•
PC with PACTware/DTM
•
Control system with EDD
8.3
Asset Management function
The instrument features self-monitoring and
diagnostics according to NE 107 and VDI/
VDE 2650. In addition to the status messages
in the following tables there are more detailed
error messages available under the menu item
"Diagnostics" via app or PACTware/DTM.
Status messages
The status messages are divided into the
following categories:
•
Failure
•
Function check
•
Out of specification
VEGAPULS WL S 61 • 4 ... 20 mA
8 Diagnosis, asset management and service
•
Maintenance requirement
and explained by pictographs:
1
2
Abb. 29: Pictographs of the status messages
1
Failure - red
2
Out of specification - yellow
3
Function check - orange
4
Maintenance - blue
Failure: Due to a malfunction in the instrument,
a failure message is outputted.
Function check: The instrument is in operation,
the measured value is temporarily invalid (for
example during simulation).
Out of specification: The measured value is
unstable because the instrument specification is
exceeded (e.g. electronics temperature).
Maintenance: Due to external influences, the
instrument function is limited. The measure-
ment is affected, but the measured value is still
valid. Plan in maintenance for the instrument
because a failure is expected in the near future
(e.g. due to buildup).
Information:
The status messages are always active.
They cannot be deactivated by the user.
Failure
The following table shows the error codes and
text messages in the status message "Failure"
and provides information on causes as well as
corrective measures.
Code
Reason
Text message
•
F013
Sensor does
not detect an
no measured va-
echo during
lue available
operation
•
Antenna
system dirty or
defective
3
4
Removal
•
Check or
correct ins-
tallation and/
or parameter
adjustment
•
Clean or
exchange
process
component or
antenna
31