Installation; Outdoor Unit; Clearance; Location - Airwell DK 125 Manual De Instalación Y De Mantenimiento

Central de climatización split sistema
Ocultar thumbs Ver también para DK 125:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

INSTALLATION

OUTDOOR UNIT

CLEARANCE

3 m
A
800 mm
models
125
A

LOCATION

The unit must be installed on a stable horizontal base of sufficient strength to support its total operating weight.
Vibration isolation devices (e.g. rubber shock absorbing pads) must be fitted between the unit and its load bearing
structure.
The unit must not be installed in a location exposed to major roof rainfall drainage and must be above ground
level if installed in an area subject to rainwater flooding. The unit must be installed at a height sufficient to ensure
proper drainage of de-icing water and to allow any possible ice build-ups to fall off the cooling battery during
de-icing cycles.
minimum recommended height is :
When locating unit give consideration to, and locate unit as remote as possible from neighbour's sleeping areas
to minimise noise.
Service and air flow clearances must be allowed as indicated on the unit dimension sheet. It should be noted that
major service may require removal of the top panels. particular attention should be paid to avoiding obstructions
to the vertical condensor or air discharge which may result in recirculation of the outdoor air.
In addition to the service clearances noted on the dimension sheet it is essential that provision is made for adequate
and safe service access.
A
A
A
minimum free clearance (mm)
155
185
205
255
500
250 mm above ground level.
10
3 m
A
305 405m 405
505
A
A
605
755
905
800

Publicidad

Tabla de contenido
loading

Tabla de contenido