INDOOR UNIT LOCATION
WARNING :
Indoor units are supplied with a charge of dry nitrogen at 40 psi.
The indoor unit is designed for installation in a suspended ceiling, supported by 4 anchoring points that enable it
to be attached and levelled.
The unit must not be located in zones containing, smoke, odours or dust that would clog the intake filters, reduce
system performance and have a negative effect on the treated air quality.
75mm
As illustrated on the diagram, the siphon to be made on site (30 mm minimum) is located on the condensate
evacuation pipe, in order to guarantee drainage when the indoor fan is in operation.
Lift the unit up to install the condensate evacuation pipe siphons.
Evacuation orifice : Ø 5/8" (125 / 185)
Evacuation orifice : Ø 7/8" (205 / 255)
Evacuation orifice : Ø 1" (305 à 905)
WARNING :
Never braze the condensate evacuation pipe to the unit's outlet connectors.
It is advisable to install a flexible sleeve on the duct to prevent any noise from being transmitted to the treated air side.
NB
In the case of the indoor unit being installed in a zone with high relative humidity, additional unit insulation should
be provided to protect the unit against risks of condensation.
75mm
Right or left exit
Unit access hatch