Caution
Use of wire size smaller than listed will void warranty.
Notes:
If aluminum conductors are used, multiply lengths by 0.5. Maximum allowable length of aluminum
is considerably shorter than copper wire of the same size.
The portion of the total cable which is between the service entrance and a ∅3 motor starter should
not exceed 25 % of the total maximum length to assure reliable starter operation. Single-phase
control boxes may be connected at any point of the total cable length.
Cables #14 to #0000 are AWG sizes, and 250 to 300 are MCM sizes.

10.6 Approvals

SP 4"
SP 4" pump end
MS6 motor
MS 4000 motor
MS 402 motor
28
Three-phase motor maximum cable length [ft]
(Motor to service entrance) (2)
2530
1480
2330
1060
1680
2650
780
1240
1950
530
850
1340
2090
650
1030
1610
520
830
1300
680
1070
790
2520
2030
3110
1670
2560
3880
1240
1900
2860
3510
1000
1540
2310
2840
850
1300
1960
2400
1060
1600
1970
1190
1460
WATER QUALITY
DRINKING WATER
SYSTEM COMPONENTS
ANSI/NSF 61
65 GM
30 °C / 86 °F
PUMP END ONLY
3420
2890
3500
2380
2890
3290
1770
2150
2440
2790
IAPMO
File 6591
0.25 % Lead