Adjustment Etw - Rechner Sensors EasyTeach P3 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Adjustment ETW - for output function antivalent
Attention:
Do not change the distance to the detecting object or the filling level during the adjustment
The EasyTeach-Adjustment provides the possibility for full or empty adjustment. We recommend, always
to do the FULL ADjUSTMENT. Ensure that the active area of the sensor is in contact with the
product to be detected or the product is placed in the active area of the sensor. The full adjustment does
not require an empty adjustment beforehand. When the adjustment with the product to be detected is not
possible, an empty adjustment can be made, e. g. the product to be detected is not known at the time of
the sensor adjustment, but an overfilling must be excluded. When the level is filled for the first time, we
recommend making a full adjustment so that the sensor is optimally adjusted on the material to be detected.
Empty adjustment - Active surface free
• The active surface of the sensor is free
• Activate the EasyTeach menu and keep it active until the LED flashes green (see EasyTeach-Chart).
The output A2 pulses accordingly
• Disconnect the wire
• During the initialization process the LED is flashing green with higher frequency. The output A2 pulses
accordingly
The empty adjustment is finished when the LED is static green. With this adjustment the sensor has
the largest sensing distance that is possible at the current mounting position. The switching hysteresis
is calculated automatically.
FULL ADjUSTMENT - Active surface covered
• The active surface of the sensor must be covered completely with the product to be detected or the
product must be in the desired position
• Activate the EasyTeach menu and keep it active until the LED flashes yellow (see EasyTeach-Chart).
The output A1 pulses accordingly
• Disconnect the wire
• During the initialization process the LED flashes yellow with higher frequency. The output A1 pulses
accordingly
The full adjustment is finished when the LED is static yellow. The sensor is now optimally adjusted for
the detection of the product currently being used and the current mounting conditions. The switching
hysteresis is calculated automatically.
Test function
The test function can be used to check that the sensor is connected correctly.
• Activate the EasyTeach menu and keep it active until the LED flashes green and yellow at the same
time (see EasyTeach-Chart)
The test function switches the output A1 and A2 ON and OFF at the same time. The test function is
activated until you disconnect the EasyTeach-Wire. The adjusted values stay unchanged.
i
After making the adjustment put the EasyTeach-Wire on GND of the supply voltage (U
This prevents unintentional adjustments on the device.
-).
B
29

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido