Rotex GW-30 C22 Instrucciones De Instalación página 102

Ocultar thumbs Ver también para GW-30 C22:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 270
side.
8.3.8
CH installation stays warm unwanted
Possible causes:
Room thermostat/weather dependent regulation
faulty or short circuited.
No È
CH installation is heated due to Tap comfort.
The service display regularly shows code 7.
8.3.9
A-label pump LED flashes intermittently red/green
Possible causes:
Too high or too low mains voltage.
No È
Pump temperature is too high.
8.3.10 A-label pump LED flashes red
Possible causes:
Pump stopped.
Solution:
Check the wiring.
Check OpenTherm, On/off connection of the unit, or the connection between CH
Yes Æ
boiler and RF room thermostat. Replace the thermostat.
Replace the weather-dependent regulation.
Unwanted circulation in the CH circuit due to thermosiphon effect or second pump in
Yes Æ
the CH circuit. Install a check valve in case of thermosiphon effect or a two-way
valve in case of a second pump.
Solution:
Yes Æ Check the mains voltage.
Yes Æ Check the water and ambient temperature.
Solution:
Reset the pump by switching off the unit by pressing the on/off button for at least 20
seconds
(attention: if the pump has been set to continuous, the pump can only
Yes Æ
be reset by pulling the plug from the socket).
Replace the pump.
49

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Gw-30 c28Gw-30 c33Rkombg22aav1Rkombg28aav1Rkombg33aav1

Tabla de contenido