5.10.5
Securing the flue system
IMPORTANT
These regulations are typical for both concentric and parallel flue
•
systems.
The flue system must be secured to a solid structure.
•
The flue system should have a continuous fall back to the boiler (1.5° to
•
3°). N.B. Wall terminals must be installed leveled..
Only use accompanying brackets.
•
Every elbow must be secured by using the bracket.
•
Exception at connecting on boiler:If the lenght of the pipes before and after
the first elbow, are no more than 250 mm, the second element after the
first elbow has to contain a bracket.
Note: The bracket must be positioned on the elbow!
Every extension must be secured per metre with a bracket.
•
This bracket must not be clamped around the pipe ensuring free
movement of the pipe..
Make sure bracket is locked into the correct position depending on the
•
position of the bracket on the pipe or elbow:
Do not mix flue parts or clamps of different suppliers.
•
Max. distance between clamps
Vertical
Others
2000 mm
1000 mm
Divide the lengths between the brackets evenly.
•
Every system must contain at least 1 bracket.
•
Position the first clam at a maximum of 500 mm from the boiler.
•
31