Alarm list
Alarm
Display
Code
025-040
WARNING PROBE AD Inlet-
A01
Temperature
WARNING PROBE Purge Air
A02
Temperature
WARNING PROBE Dewpoint
A03
Meter
WARNING PROBE Heater
A04
Outlet Temperature 1
WARNING PROBE Heater
A05
Outlet Temperature 2
WARNING PROBE Compres-
A06
sor DischargeTemperature
WARNING PROBE Thermal
A07
MassTemperature
WARNING PROBE Capacitive
A08
Level
ALARM FRIDGE High Pressu-
A09
re by pressure switch
ALARM FRIDGE High Tempe-
A10
rature by temperature switch
WARNING ADSORBER High
A11
AD Inlet Temperature
ALARM FRIDGE Low AD Inlet
A12
Temperature
WARNING ADSORBER High
A13
Electrical Heater Temperature
Column 1
WARNING ADSORBER High
A14
Electrical Heater Temperature
Column 2
WARNING ADSORBER Low
A15
Electrical Heater Temperature
Column 1
English
ATT
ATT
ATT
Reset
060-090
140-340
A
X
X
A
X
X
X
A
X
X
X
A
X
x
X
A
X
X
X
A
Nu
X
A
Nu
X
A
NU
X
A
X
X
A
X
Nu
A,
X
X
se T<13°C(**)
A
X
X
A,
X
X
X
se T<150°C(**)
X
X
X
X
A, T>(setpoint
X
X
X
resistenza – 30
+ 20) (**)
Delay
Defoult conditions to active the alarm
AIN Ad Inlet Temperature
4 s
AIN Purge Air Temperature
3 s
AIN Dewpoint Meter
3 s
AIN Heater Outlet Temperature A PROBE Not Connected Or Faulty
3 s
AIN Heater Outlet Temperature B PROBE Not Connected Or Faulty
3 s
AIN Compressor Discharge Temperature
3 s
AIN Thermal Mass Temperature PROBE Not Connected Or Faulty
3 s
AIN Capacitive Level
3 s
DIN High refrigerant pressure switch Active
Immediate
DIN High Temperature switch Active
Imm.
180s
180s
5s
A, se
T<150°C
(**)
600s
ATT140-340
Stop
Compressor
5s
Stop Dryer
Alarm
relay
Y
N
Active
N
N
Active
N
N
Active
N
N
Active
N
N
Active
Y
N
Active
N
N
Active
N
N
Active
Y
N
Active
Y
N
Active
N
N
Active
Y
N
Active
N
N
Active
N
N
Active
N
N
Active
9 / 14