FINAL CHECKS AND TESTING
Before powering the control unit:
- Check proper setting of the dip switches.
- Check the electrical connections. Improper connections may irreversibly damage the control unit or present a
hazard to the operator or the user.
POWER THE DEVICE
- Check that the red LEDs (DL3, DL 4) are normally on and that the yellow LED (DL2) is off.
- Check that any detection devices connected to terminals 1-4 function properly
- Check that the gate is closed and that the motors are ready for operation.
- Remove any obstacles within the range of action of the gate.
TROUBLESHOOTING
Before carrying out any operation (installation or maintenance) ensure that the power has been
cut !!
FAULT
The operator does not
open or reclose
The PHOTOCELLS do
not work
Pressing the 2nd key of
the TX the pedestrian
gate is not activated
The transmitter has
little range
POSSIBLE CAUSES and SOLUTIONS
Check that the red LEDs are on and the yellow one off.
Connect the STOP input (terminals 2-4) to an NC button or jumper it.
Connect the START input (terminals 3-4) to an NO button.
DIP6 ON. Set DIP6 to OFF and check that the LED DL4 goes off when the
photocells are blacked out.
The second channel of the transmitter has not been learned previously.
Perform the learning procedure of the second channel.
Check that the antenna has been positioned properly (braid terminal 15, signal
terminal 16, for control units code AS04330).
If a plug-in receiver is used (code AU01710), the antenna must be connected
to the terminals on the receiver. Check that there are no sources of
disturbance in the vicinity, which limit the range.