MOUNTING AND OPERATING INSTRUCTION FOR THE
SPIROVENT 'AIR
Applies to product types starting with BA and HA (see product
label
) except for BAS and HAS.
Manufacturer: Spirotech b.v. Helmond - The Netherlands
This Spirotech product is designed and manufactured accord-
ing to the Sound Engineering Practice as stated in the Pressure
Equipment Directive (97/23/EC art.3.3) adopted by the
European Parliament and the European Council in May 1997
Instruction
This instruction must be given to the end user, who should keep
it.
Take into account local regulations.
Application
Fully automatic removal of air and gas from heating water,
cooling water, water/glycol mixtures and process water. Not
suitable for demineralised water, drinking water, potable water
and dangerous or inflammable substances. Do not use in com-
bination with chemical additives.
When in doubt contact your supplier.
Pressure and temperature range
From 0 to 10 bar g; from 0 to 110
otherwise on the product.
Quality control
All products are subject to final inspection procedures:
Leaktest:
De-aerating valve
Standard
Test pressure 0,5 +/- 0,1 bar
7+/- 1 bar
Test medium Air
Air
Test time
10 s
60 s
Test results No leakage
No leakage No leakage
Functional test of the de-aerating valve:
Bleeding test
Bleeding completely
Shut down test
Shutting down completely
Test results
Approved
Quality, safety and environmental aspects are managed with-
in a certified Managementsystem acc. to:
-NEN-EN-ISO 9001
-NEN-EN-ISO 14001
-TUV 18001
Installation and maintenance may only be carried out by
a competent installer.
When working on the Spirovent 'Air always make the installa-
tion pressureless and let it cool down.
Handling the Spirovent 'Air
Follow these safety procedures when lifting the Spirovent 'Air
from its packaging:
- Lifting of the Spirovent 'Air may only be carried out by com-
petent personal.
- Use approved lifting chains / straps with safety hooks.
- Sling the Spirovent 'Air as shown in figure II.
- Make sure that the lifting chains / straps are tight before lift-
ing the Spirovent 'Air.
- Do not stand under the load.
- Make sure the Spirovent 'Air can move freely.
Installing the Spirovent 'Air
The Spirovent 'Air should be installed at the hottest point of
the installation, for example in the main flow of a the central
0
C, unless explicitly indicated
Housing
p > 10 bar or T>110 C
1,5 x working pressure
Water
60 min
heating installation or in the main return in a cooling installa-
tion.
• The Spirovent must be installed stress free.
• The Spirovent may not be used to support pipework
• The operation is independent of the flow direction
• If the installation is tested with compressed air, the Spirovent
'Air should be shut off temporarily with a cap R
plied)
.
• Take care: cap R
1
/
must be removed before commissioning
2
the installation.
• Maximum allowable testing pressure 15 bar.
• Apply the separately supplied product labels if the labels on
the product are not visible, for example after the unit has
been insulated.
• The lifting lugs
may only be used for handling during
installation.
• The drain tap
fitted on the side of the product is meant for
draining large quantities of air during filling of the installa-
tion:
- Take care: hot water or steam may escape: mount a hose,
resistant to the pressure and temperature concerned, to dis-
charge the hot installation water to a suitable drain point.
- First remove the safety plug.
- Fit the discharge hose.
- Take care that the hose can not slip off.
- Open the drain tap
gradually and let all the air escape.
- Shut off the drain tap
and fit the safety cap.
- The remaining deaeration is done automatically by the
Spirovent 'Air.
Using the Spirovent 'Air
General recommendations / obligations
• It is not allowed to modify the Spirovent nor to weld to it
other than necessary for mounting the Spirovent into the
installation
• Make sure that the vent valve
the drain tap
is always accessible.
• Take care: touching the product "in operation" may cause
burns.
• The drain tap
may also be used to remove floating dirt:
- Take care: hot water or steam may escape: fit a hose resistant
to the pressure and temperature concerned, to discharge the
hot installation water to a suitable drain point.
- First remove the safety cap.
- Mount the discharge hose.
- Take care that the hose can not slip off.
- Open the drain tap
gradually for a short period.
- Shut off the drain tap
off anymore and mount the safety plug.
- Try to restrict the amount drained off water as much as possi-
ble.
- Check the installation pressure after this process and fill up if
necessary.
Guarantee
• Spirotech gives a guarantee for its products for 3 years after
the date of purchase.
• Incompetent use, incorrect installation and attempts to do
repairs oneself make any claim under the guarantee invalid.
• DAMAGE OR LOSSES RESULTING FROM FAILURES are not
included in the guarantee.
• Alterations reserved
Failures
• When the Spirovent 'Air has been stored or mounted verti-
cally, but not filled, for a longer period of time, the vent valve
may leak for a short while. This will stop very quickly.
• Always contact your installer in case of malfunction.
• In case of leakage of the vent valve, the complete deaeration
cap must be replaced.
5
UK
1
.
1
/
(not sup-
2
as soon as no air escapes anymore
is always left clear and that
as soon as no floating dirt is drained