Carrier 10TE Manual Del Usuario página 23

Intercambiadores de placas y juntas
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 74
50/50 proportion of H and L plates
Product picture - black and white
with Carrier logo on it
5%-45% proportion of H plates
5.11 - Increasing the transfer area
It is possible to add an even number of extra plates to an exi-
sting heat exchanger, provided you:
• Check the maximum plate capacity of the heat exchanger.
• If the length is insufficient, provide new carrying bars and
threaded rods.
INSTALLATION, OPERATION AND
M A I N T E N A N C E I N S T R U C T I O N S
Product title
CARRIER Model code
Nominal cooling capacity xxx - xxx kW
xx Hz
Product logo
- black and white
Original document
• Replace the data plate and the plate arrangement drawing
with the new ones provided by CARRIER.
• Leaks often occur when plates with new gaskets and plates
with old gaskets are used together (due to difference in tough-
ness). We therefore strongly recommend replacing all worn
gaskets with new ones.