Fault: Backwash/rinse cycle cannot be started manually.
Possible causes
Incorrect contact connected to
the pressure switch.
Fault: Valve is in the FILTER position, however water is flowing to
the sewage (inspection glass).
Possible causes
–
Contamination through
small parts or sand.
–
Valve seal loose or worn.
Cam disc is not set correctly.
Fault: Pool loses considerable water over time.
Possible causes
Unfavourable installation
conditions.
Please be aware that unintentional drops in the water level
can cause overlying roll-up covers to break. If necessary,
these should open automatically.
7.2
Replacing parts/modules
7.2.1
Replacing the upper part
Only very few wear parts on the device can be replaced. The
reason being that there are parts/modules which are fitted
together and must be set up exactly as a whole. The
manufacturer has the knowledge required for the exact set-up.
05|2018
Faults/troubleshooting
Remedy
Reconnect the pressure
switch; use contacts 2 and
3. (Looking at the
pressure switch with the
contacts underneath,
these are the middle and
left contacts.)
Remedy
Remove the valve lid and
find the cause of the
overload. Clean the valve
if necessary.
Remove the complete
upper part and send it to
the manufacturer.
Remedy
Check the installation
situation. If necessary,
install a special SPECK
non-return-valve
(240.9102.063).
EN 35