4
Electrical installation
Wiring
Terminal assignment
Motor temperature monitoring
Terminal X106
Terminal data
Flexible
With wire end
ferrule
Motor brake control (optional)
Observe the notes in the Mounting Instructions on the motor brake
control.
Terminal X107
Terminal data
Flexible
With wire end
ferrule
46
Labelling
Description
T1
Motor temperature monitoring with PTC element
(type-A sensor, switching performance according to
T2
EN 60947-8 for type-A tripping units) or thermostat
(NC contact).
SSP940X106
Max. conductor cross-section
2
[mm
]
[AWG]
2.5
12
Labelling
Description
Connection of the motor holding brake
BD1
+ (Lenze: WH)
BD2
- (Lenze: BN)
E94AZHX0051: 24 V DC, max. 2.5 A
Observe correct polarity!
+ / -
Supply voltage for the motor holding brake (18 ...
30 V DC)
Observe correct polarity!
SSP940X107
Max. conductor cross-section
2
[mm
]
[AWG]
2.5
12
Tightening torque
[Nm]
[lb-in]
0.5 ... 0.6
4.5 ... 6.2
Tightening torque
[Nm]
[lb-in]
0.5 ... 0.6
4.5 ... 6.2
EDK94ZPM113 DE/EN/FR/ES/IT 1.0
Screw driver
PZ0
Screw driver
PZ0