Commissioning; Possible Settings Via Dip Switch - Lenze E94AYCDN Instrucciones Para El Montaje

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

7

Commissioning

Possible settings via DIP switch

7
Commissioning
Possible settings via DIP switch
Via the DIP switches on the front, the following can be set:
ƒ Station address using switches 1 ... 32 ("MAC ID" area)
ƒ Baud rate using switches 1 and 2 ("Baud" area)
Pos.
Switch positions
Baud rate
2
S225
OFF
OFF
ON
ON
)
Note!
Please observe the information about the setting of the DIP switches given in
the "Commissioning" and "Appendix" chapters of the E94AYCDN
communication manual (DeviceNet).
40
1
kbps
OFF
125
ON
250
OFF
500
ON
No function
Node address (MAC ID)
32
16
The station address results from the sum of the
binary values of switches 1 ... 32.
l
Example: Station address 44
W
switches 32, 8, 4 = ON (32 + 8 + 4 = 44)
l
Valid address range: 0 … 63
l
The Lenze setting for all switches is OFF.
l
8
4
2
EDK94AYCDN DE/EN/FR/ES/IT 4.0
E94YCDN001D
1