SE: Sewage
bS: Pressurisation (booster)
5.
Press (5) to confirm
6.
1P or 2P are shown on the display.
7.
Press (1) or (2) to edit the number of pumps:
1P= one pump
2P= two pumps
8.
Press (5) to confirm
9.
Turn the control panel off and then on again.
The new application is now activated.
5.4.4

Parameter menu

Only in STANDBY mode (StY) is it possible to select
the operation parameters (see
NOTICE:
After 3 minutes of inactivity and if no button is
used, automatic mode is restored.
The pump remains in standby during configuration.
Refer to figures
1
and
2
1.
Press and hold (4) to access STANDBY (StY)
mode.
2.
LEDs (2) and (5) switch off. LED (9) is ON.
3.
Press (5) to access the parameter menu.
"000" flashes.
4.
5.
Press (1) or (2) to edit the password 066.
6.
Press (5) to confirm. If password is wrong press
(4) for read-only mode.
7.
Press (1) and (2) to view the parameter
8.
Press (5) to edit the parameter. It flashes.
9.
Press (1) or (2) to modify the value.
10. Press (5) to confirm.
11. Press (1) or (2) to confirm and move on to the
next parameter or press (4) for AUTOMATIC or
MANUAL mode.
12. Repeat points 7 to 9.
13. Press (4) for AUTOMATIC or MANUAL mode.
Tab 2
SEWAGE Application
(parameter SE is selected, section 5.4.3)
Par.
Description
Range
SYSTEM
c01
Number of
1= 1 pump
pumps
2= 2 pumps
c02
Filling func-
0= Disabled
tion.
1= Enabled
(See Fig-
ures
48
to
52
and
58
to
62)
c03
Type of
1= Float
sensor that
switches
is used.
2= Sensor
level
Tab 2
or
Tab
3).
Unit
Default
-
depend-
ing on the
control
panel
model
-
0
-
1
3= Probes
4= Level
sensor with
automatic
switching to
float if sen-
sor is faulty
5= Level
sensor with
automatic
switching to
probes if
sensor is
faulty
c04
Sensor sig-
1= 4-20mA
nal type
2= 0-20mA
c05
Initial scale
Pressure:
value of the
0 to 60 bar
sensor. Only
Tempera-
if sensor is
ture:
used.
-20 to 100°C
Level:
0 to 50 m
r05
Calibration
0= Disabled
of the initial
1= Enabled
scale in mA.
t05
Software
Standard
filter for ana-
Lowara
logue input
c06
Full scale
Pressure:
value of the
0 to 60 bar
selected
Tempera-
sensor. Only
ture:
if sensor is
-20 to 100°C
used.
Level:
0 to 50 m
THRESHOLD AND TIMING (threshold is active
only with sensor)
c07
Unique level
0= Disabled
set point
1= Enabled
r07
Set point
0 to Full
level value
Scale
r08
Upper
0 to Full
threshold
Scale
delta
r09
Lower
0 to Full
threshold
Scale
delta
r10
Upper
0
threshold
Scale
Start Pump
1
t10
Delay time
0 to 100
start Pump 1
r11
Lower
0
threshold
Scale
Stop Pump
1
t11
Delay time
0 to 100
stop Pump 1
r12
Upper
0
threshold
Scale
en - Original instructions
-
1
vari-
0
ous
-
0
-
3
Vari-
10.0
ous
-
0
Vari-
5
ous
Vari-
0.5
ous
Vari-
0.5
ous
to
Full
Vari-
8
ous
sec
0
to
Full
Vari-
2
ous
sec
0
to
Full
Vari-
7
ous
41