en - Original instructions
6= Maxi-
mum pres-
sure
threshold
alarm.
7= Mini-
mum pres-
sure
threshold
alarm.
8= External
alarm
9= Com-
mand for
Auto-test
10= Auto-
test faulty
11= Power
ON
c41
Configura-
See config-
tion of the
uration c40
OUT_2
relay (K4 on
board)
c42
Configura-
See config-
tion of the
uration c40
OUT_3
relay (K5 on
board)
c43
Configura-
See config-
tion of the
uration c40
OUT_4
relay (K6 on
board)
c44
Configura-
See config-
tion of the
uration c40
OUT_5
relay (K7 on
board)
c45
Configura-
See config-
tion of the
uration c40
OUT_6
relay (K8 on
board)
MODBUS Q-SMART MODULE
Programming the field modbus RTU RS485
(refer to figures
7
and 10)
Note: With Even or Odd parity there is one stop bit,
with no parity there are two stop bits.
c46
Enable
0= Disa-
ModBus
bled
port com-
1= Enabled
munication
r46
Setting the
1 to 255
address
c47
Parity
0= None
1= Even
2= Odd
r47
ModBus
0= 9600
Speed
1= 19200
2= 38400
52
-
0
-
0
-
0
-
0
-
0
-
0
-
247
-
2
-
1
3= 57600
DEFAULT SETTING
c48
Loads all
0= No
the default
1= Load
parameters
default
(factory
setting)
HOUR COUNTER
h49
Reads
-
pump 1
operating
hours
h50
Reads
-
pump 2
operating
hours
h51
Reads total
-
hours of
power of
control
panel Q-
SMART
c52
Resets
0= No
memory of
1= Reset
the hour
pump 1
counter for
operating
all pumps
hours
2= Reset
pump 2
operating
hours
3= Reset
pump 1 +
pump 2
operating
hours
PROGRAMMING THE ALARMS
(alarms dedicated to sewage application)
c53
Lack of
0= Disa-
water
bled
alarm. Pro-
1= Enabled
tection
against dry
running of
the pump
r53
Setting
5 to 100
probe sen-
sitivity ac-
cording to
water con-
ductivity.
t53
Delay time
0 to 200
until activa-
tion of lack
of water
alarm (c53)
c54
Enable
0= Disa-
alarm for
bled
-
0
-
0
-
1
KΩ
5
sec
0
-
0