en - Original instructions
c38
Configura-
0= Not
tion of pro-
used.
grammable
1= External
digital input
command
D IN_PROG
and the
(1)
pumps are
switched on
one at a
time (2 sec-
onds apart).
2= External
alarm
3= External
ON/OFF.
4= Change
set point
r38
Setting the
1= NC,
logic of pro-
Normally
grammable
closed
digital input
2= NO,
D IN_PROG
Normally
open
t38
Delay time
0 to 200
until activa-
tion of pro-
grammable
digital input
D IN_PROG
(r38)
6CP Q-SMART MODULE (OPTION ACCESSO-
RY),
It is an electronic card with six relays and voltage-
free contacts (refer to figures 7, 9).
c40
Configura-
0= Disabled
tion of
1= P1 run-
OUT_1
ning
relay (K3 on
2= P2 run-
board)
ning
3= Fuse 1
burned
4= Fuse 2
burned
5= High
level alarm
6= Alarm
Max level
threshold
7= Alarm
Minimum
level thresh-
old
8= External
alarm
9= Auto-test
in progress.
10= Alarm
sensor fault
11= Power
ON
c41
Configura-
See configu-
tion of
ration c40
OUT_2
relay (K4 on
44
-
0
-
1
sec
0
-
0
-
0
board)
c42
Configura-
See configu-
tion of
ration c40
OUT_3
relay (K5 on
board)
c43
Configura-
See configu-
tion of
ration c40
OUT_4
relay (K6 on
board)
c44
Configura-
See configu-
tion of
ration c40
OUT_5
relay (K7 on
board)
c45
Configura-
See configu-
tion of
ration c40
OUT_6
relay (K8 on
board)
MODBUS Q-SMART MODULE
Programming field modbus RTU RS485
(refer to figures
7
and 10)
Note: With Even or Odd parity there is a one stop
bit, with no parity there are two stop bits.
c46
Enable
0= Disabled
ModBus port
1= Enabled
communica-
tion
r46
Setting the
1 to 255
address
c47
Parity
0= None
1= Even
2= Odd
r47
ModBus
0= 9600
Speed
1= 19200
2= 38400
3= 57600
DEFAULT SETTING
c48
Loads all the
0= No
default pa-
1= Load
rameters
default
(factory set-
ting)
HOUR COUNTER
h49
Reads pump
-
1 operating
hours
h50
Reads pump
-
2 operating
hours
h51
Reads total
-
hours of
running of
Q-SMART
control pan-
el
-
0
-
0
-
0
-
0
-
0
-
247
-
2
-
1
-
0