COMMUNICATIONS
FE Connect Mobile Application
Underload
These settings replace the Underload potentiometer when using the FE Connect mobile app for setup. In
addition, the app provides more detailed control of the feature.
Underload, Off Time
Prime Delay (Surface applications only): Selectable from 0 to 5 minutes.
Refer to
"Underload Sensitivity" on page 27

Duplex Alternator

Configuration: This selection enables the duplex feature and sets the identity
of each drive in the network.
Standalone (drives will operate independently)
Pump 1
Pump 2
Switching Interval: This parameter sets the run time (hours) before the lead
and lag roles alternate. The Pump 1 drive setting controls the entire system.
1 to 24 hours
Default = 1 hour
Refer to
"Duplex Alternator Feature" on page 38
using the Duplex Alternator feature.
Advanced Options
Pressure Bump Mode: Bump mode controls how hard the drive will pump just before stopping the motor
when the pressure setpoint is reached.
For applications with a large pressure tank, or if the system takes too long to stop, the bump mode can be
modified to be more aggressive. The system behavior should be monitored when adjusting these settings to
ensure proper operation.
Standard, Aggressive, or Off.
Tank Size: Use this setting to refine system performance when using a standard pressure sensor. Select
either:
Small Tank, Large Tank
Steady Flow: Select either Normal Performance or Reduced performance.
Refer to
"Steady Flow Selection (DIP SW1 – Position 4)" on page
Broken Pipe Detection: Use this selection to enable or disable the feature, as well as adjust the length of
time before the fault occurs.
Refer to
"Broken Pipe Protection" on page
Wet Floor Detect Input: This parameter controls how the controller will react when the Wet Sensor control
terminal is used.
Fault with High (default). This supports the Franklin Electric Moisture Sensor device.
Fault with Low. This can be used with other unpowered dry contact switched input devices.
Refer to
"Moisture Sensor" on page 29
34
for more information.
for more information about
28.
30.
for more information.