Connection of control panel

4.3.1

Electrical feed

The electrical power supply of the control panel is done by Figure 5 terminal A with a
voltage of 110 ~ 230V ± 10% 50 - 60 Hz. The connection must be made by 3 wires with a
minimum diameter of 1.5 mm, being mandatory the connection of the ground wire to the
supply terminal A. The wire line passes through a fuse. The maximum power
consumption for a control panel is 70 W. The connection will be made according to the
label on the bottom of the chest.
DISCONNECT the mains voltage and batteries before
Do not cut the power supply during the boot process.
Such action may cause control panel malfunction
4.3.2
Output card
2
1
The output card has the following outputs:
1. Battery.
For DVB models, this terminal is connected with the batteries. It is only active on the card C1
(See Figure 5).
Through this connection the battery is charged and monitored. The battery charge is
compensated depending on the battery temperature. This input / output is protected by a
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
Addressable Control Panel for CO and NO
Figure 6: Power supply label
working inside the control panel
4
5
3
Zone 1 or 3
Sounder connection using the alarm relay and
Figure 7: Output card layout
FIRE PROTECTION MANUFACTURER
ZafirCO
4
6
Zone 2 or 4
the 30 Vdc auxiliary outputs
2
5
6
33

Publicidad

loading