Leter
Indication
D
Test mode
E
Manual ventilation
F
ALARM
G
Power supply
H
Battery
I
General fault
J
Supply fault
K
System fault
L
Z1 Fault/Disabled
M
Z2 Fault/Disabled
N
Z3 Fault/Disabled
O
Z4 Fault/Disabled
38
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
Addressable Control Panel for CO and NO
ZafirCO
Direct function that impose activation of all zones in test
mode.
► Led ON: All zones in test mode. The Leds L, M, N and
O that are active will be turned off.
► Led OFF: function of all zones in test mode
deactivated. L, M, N and O leds return to normal
operation.
Note: This function works independently to individual
mode tests selection of each zone, which is accessible
through the menu of the control panel, in which each
zone in test is indicated by double flashing led L, M, N or
O corresponding to each zone. See Section 10.8.
Active/Des-active ventilation of all zones.
► 1 Press: Active ventilation of all zones.
► 2 Press: Activate the vent 1 and 2 of all zones (DVB
model only).
► 3 Press: Ventilation output in automatic mode.
Through the control panel menu it is allowed selection of
manual or automatic activation of each zone
Leds:
► ON: Some zone with Ventilation Output 2 (models
DVB) permanently activated.
► Flashing: Some zone with Ventilation 1 (DVB models
only) permanently activated.
► OFF: Ventilation outputs in automatic mode.
Some zone in Alarm status.
System fed by external electrical power supply.
System fed by batteries.
Fault in the system. More information accessing at the
display.
General supply fault. More information accessing at the
display.
The system has sttoped working properly.
Zone 1 in fault, disabled or test.
► Led ON: Zona disabled.
► Led flashing: Zone with fault.
► Led with double flashing: Zone in test mode selected
individually through the menu of control panel. For going
out of the test mode of the zone, it must be actived
through the menu of control panel. Test indication is over
fault indication.
Note: See key "D". See chapter 10.8.
The same functionality than "L" but applied to zone 2.
The same functionality than "L" but applied to zone 3.
The same functionality than "L" but applied to zone 4.
FIRE PROTECTION MANUFACTURER
2
Description