5) Operation of Battery
If control panel is DVB, disconnect the main power supply. The control panel must activate the
buzzer, turn off the led "Red" (letter G in Figure 10), and turn on the led "Batteries" (letter H of
Figure 10).
After verifying that the system is stable and remains working normally, reconnect the main
power supply. The battery led (letter H of Figure 10) must be switch off and the led (Led G of
Figure 10) on.
9.3
Sensors (each 12 months)
Maintenance operations to be performed on the sensors are the followings:
1) Date of manufacture
Check the date of manufacture of the sensor. If exceeded their lifetime, it must be replaced.
Note: See Chapter 3 to take into account the storage and installation time.
2) Check sensor operation
Put zones in test mode by pressing the "test mode" (letter D of Figure 10) in control panel. In
this mode, the sensor led behavior is modified and all relays of all zones are disabled.
Face each sensor to test gas (at least 100 ppm of CO or 2 ppm of NO
double flash, indicating that it has detected the rising concentration of toxic gas.
The control panel allows also to test by zone through the menu 5 (Chapter 10), option 4, or
disable it with option 5.

10 Menu.

Control panel menu is accessible pressing MENU key (Key R of figure 10):
Menu 1
1. Monitoring
2. System setup
3.System test
4. Leds activation
5. General relays status
Hereafter are described different options:
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
Addressable Control Panel for CO and NO
Menu 2
1. Configure
Menu 3
1. Configuration summary
2. Points setup
3. Zones setup
2. Time and date
Menu 6
1. Change date
2. Change time
3.Languagues
4. Password
Menu 7
1. Password level 2
2. Password level 3
5.Ask version
Menu 8
1. Activation by sensor
2. Activation by zones
FIRE PROTECTION MANUFACTURER
ZafirCO
). The sensor will perform
2
Menu 4
1.Get by programming
2. Get by point number
Menu 5
1. Activation parameters
2. Disable zone
3. Enable zone
4. Zone in test mode
5. Active zone
6. Edit zone
2
43