10.1 Monitoring
Option 1 of menu 1. Allows to display information of the concentration sent by the sentor to
control panel.
L A B E L
C : 0 3
Z n : 0 1
V a l u e s :
[
- LABEL: Name or reference associated to sensor within the facility for easily identify. By
default, it is the value of the control panel, zone and point (Ex: C: 01Zn02Pt04).
- Type: Type of sensor.
- C: Zn: Pt: Control panel, Zone and Point.
- St: sensor Status: Repose or Alarm.
- Pn: Program number of the sensor.
- Values: Values of the last four instantaneous concentration sent by the sensor. This value is
sent each 10 s approximately to control panel, and it is used for the actuation of the alarm relay
and display on the screen when in alarm status.
- Average: Value of the last average concentration sent by the sensor. This value is sent each
50 s approximately to control panel, and it is used for the actuation of ventilation relays and
display on the screen if the zone is not in alarm status.
10.2 Configuration summary
Option 1 of menu 3. In this menu, it is shown the information of sensors configured in each
zone.
S U M M A R Y :
Z O N E S
:
0 0 4
P O I N T S :
0 1 5
10.3 Get by programming / Get by point number
Option 1 and 2 of the menu 4. In this menu you can view the information of the points of a zone
ordered by point number (option 1) or by programming number (option 2).
On this information it is possible to modify the program number, add a new point (modifying a
point of a zone with programmation number "0"), delete a point (modifying the programmation
number of the point by the number "0") or introduce the label (through the display of control
panel or the "I-Link CO" program for PC.
The "I Link CO" program is installed on PC with at least Windows 7 operating system, and it
allows writing labels on tables depending on the zone and point number, and download it to the
control panel connecting the PC to the panel with cable USB type A connector on one end (to
connect to the pc) and B type in the other (to connect to the control panel).
Note: When control panel is connected or reseted, it performs a search of the sensors
connected to the zones. If this configuration is accepted, it overwrites the memory
loosing the previous ones. If you want to keep the labels configured, you should not
accept the new configuration. This will be returned to the existing configuration with
their labels, and from here, you should use the options discussed to introduce new
sensors (Add, delete, change).
44
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
Addressable Control Panel for CO and NO
P t : 0 0 2
S t : R E P O S E
0 1 0
0 1 2
0 1 2
: Z o n e 1  Z o n e 2  Z o n e 3  Z o n e 4 
C O
:
0 0 3
N O 2 :
0 0 0
FIRE PROTECTION MANUFACTURER
ZafirCO
T y p e : S C O
P n : 5 5 8 2 6
0 1 1
]
A v e r a g e : 0 1 5
0 0 4
0 0 3
0 0 0
0 0 0
2
0 0 5
0 0 0