INSTRUCTIONS FOR USE
The minimum length of the insulating element and the
dielectric properties of the insulating pole must be used
with the independent voltage detector.
"D" LIMIT DISTANCES OF WORK ZONES AT AN
UNPROTECTED VOLTAGE POINT
Un
Un
Nominal
Tensión
Working with
Trabajo en
voltage in
(Voltaje)
live voltage
thousands
nominal
en miles
of Volts
PERSONAL
QUALIFIED
de Voltios
CUALIFICADO
PERSONNEL
< 1 kV
3 kV
6 kV
10 kV
15 kV
20 kV
30 kV
45 kV
66 kV
110 kV
132 kV
220 kV
380 kV
Dpel-1
Dpel-1
Tensión
SÓLO
ONLY
50 cm
62 cm
62 cm
65 cm
66 cm
72 cm
82 cm
98 cm
120 cm
160 cm
180 cm
260 cm
390 cm
Dpel-2
Dpel-2
Distancia
Danger
de Peligro
distance
de trabajos
of works
close-by
en
proximidad
50 cm
52 cm
53 cm
55 cm
57 cm
60 cm
66 cm
73 cm
85 cm
100 cm
110 cm
160 cm
250 cm
24
Dprox-1 Dprox-2
Dprox-1 Dprox-2
70 cm
300 cm
112 cm
300 cm
112 cm
300 cm
115 cm
300 cm
116 cm
300 cm
122 cm
300 cm
132 cm
300 cm
148 cm
300 cm
170 cm
300 cm
210 cm
500 cm
330 cm
500 cm
410 cm
500 cm
540 cm
700 cm