To remove the circuit breaker from inside the removal carriage, place it in the REMOVED
(DISCONNECTED) position. Greater details regarding the removal procedures may be found
on page 23. Pull the tracks totally out, fit the removable hooks on the side of the circuit
breaker (as indicated for the fixed circuit breaker) and suspend it by means of a winch.
Other important recommendations:
When moving the circuit breaker, do it slowly, avoiding impacts to it;
Do not pass ropes or cables through the removable hooks or through the suspension
grommets of the removal carriage. Always use locking safety hooks, suspending it by
means of a winch:
The suspension cables must not be less than 45º from horizontal.
1.8 StorAge
If there is a need to store the circuit breaker before its installation, keep it in its original packaging,
in a clean, dry, ventilated and heated place to avoid condensation.
When it is no longer in its original packaging, protect it from dust or humidity covering it with a
plastic film or tarpaulin. Do not store the circuit breaker in an uncovered place or exposed to
adverse weather conditions.
AttentIon!
Be sure to maintain the circuit breaker, when stored, in the OFF condition,
and with the SPRINGS DISCHARGED, which may be checked through the
front indicators, in accordance with the figure below:
CIRCUIT
BREAKER OFF
Removable Circuit Breakers must be stored in a level place, in the TEST position.
TEST POSITION
English
open Circuit Breaker
SPRINGS
DISCHARGED
ABW | 21