AttentIon!
Before pulling the circuit breaker, check if the removal carriage is fastened
to the panel. If not, hold it so that it does not fall over with the weight of the
circuit breaker.
In the REMOVED position, the power and control circuits are disconnected.
removal – Circuit Breakers ABW40...50
Press the off button to turn off the circuit breaker.
Locate and loosen the side fasteners, using the removal rod itself, and pull them upward,
releasing the circuit breaker.
Then follow procedures E2), E3) and E4), described above to bring the circuit breaker to
the TEST position.
Repeat these same procedures to bring it to the REMOVED position.
LOOSE
FASTENER
English
open Circuit Breaker
ABW | 25