Information
"Use 60/75°C copper field wiring conductors."
„These products are intended for use in a pollution degree 2 environment"
"Maximum ambient temperatur 50°C"
"The source shall be derived from a non-corner grounded type TN with max. Impulse Voltage of 4 kV and not
exceeding 289 V phase to earth or from IT source with max. Impulse voltage of 6 kV not exceeding 500 V (or
equivalent) or devices with the suffix –IT."
Size
valid
1
generally valid
Motor
group
installation
(Group fusing):
differing
data
CSA:
1)
( 7.2)
BU 0155 es-3520
Only for use with Connectors from HARTING ELECTRIC GMBH & CO KG, LQ Mechatronic
Systems GmbH and Intercontec Produkt GmbH: "Suitable For Use On A Circuit Capable Of
Delivering Not More Than 5 000 rms Symmetrical Amperes, 500 Volts Maximum" "When
Protected by class RK5 Fuses or faster.
"Suitable For Use On A Circuit Capable Of Delivering Not More Than ________ rms Symmetrical
Amperes, 500 Volts Max., When Protected by High-Interrupting Capacity, Current Limiting Class
CA, CC, CF, G, J, T Fuses." The short circuit rating (max. 65 000A) is based on the Connectors
(Details listed below) and will be printed during production. Details listed in
"Suitable For Use On A Circuit Capable Of Delivering Not More Than ______ rms Symmetrical
Amperes, 500 Volt maximum"
"When Protected by Circuit Breaker (inverse time trip type) in accordance with UL 489" The short
circuit rating (max. 10 000) is based on the Connectors (Details listed below) and will be printed
during production. Details listed in
Only for use with Connectors from HARTING ELECTRIC GMBH & CO KG, LQ Mechatronic
Systems GmbH and Intercontec Produkt GmbH: "Suitable for motor group installation on a circuit
capable of delivering not more than 5000 rms symmetrical amperes, 500 V max" "When
Protected by class RK5 Fuses or faster, rated max. 30Amperes", as listed below.
"Suitable for motor group installation on a circuit capable of delivering not more than _______rms
symmetrical amperes, 500 V max" "When Protected by High-Interrupting Capacity, Current
Limiting Class CA, CC, CF, G, J, T Fuses, rated max. 30A". The short circuit rating (max. 65 000
A) is based on the Connectors (Details listed below) and will be printed during production. Details
listed in
.
1)
"Suitable for motor group installation on a circuit capable of delivering not more than _______rms
symmetrical amperes, 500 V max" "When Protected by Circuit Breaker (inverse time trip type) in
accordance with UL 489, rated max. 30 Amperes" The short circuit rating (max. 10 0000) is based
on the Connectors (Details listed below) and will be printed during production. Details listed in
None differing data equal to UL
1 Información general
description
1)
.
1)
.
1)
.
21