Code 85 (Internal Fault); Code 117 (Door Opened); Code 159 (Communication Error Cimxxx); Code 163 (Drive Unit Configuration Fault) - Grundfos LC 231 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Remedy
Replace the control unit.
Contact Grundfos or an
authorised service workshop.

8.16 Code 85 (Internal fault)

Alarm code 85 is shown on the display.
The alarm symbol on the display turns red and
the pump stops.
Alarm code Drive unit memory fault is
displayed in Grundfos GO Remote.
Cause
Internal memory fault.
Remedy
Contact Grundfos or an
authorised service workshop.

8.17 Code 117 (Door opened)

Warning code 117 is shown on the display if you
press the Up or Down button.
The warning symbol on the display turns yellow
and the pump's operating mode is unchanged.
Warning code Door opened is displayed in
Grundfos GO Remote.
Cause
The door to the control-unit
room has been opened.
Remedy
Check the room with the
control unit.
8.18 Code 159 (Communication error
CIMxxx)
Warning code 159 is shown on the display if you
press the Up or Down button.
The warning symbol on the display turns yellow
and the pump's operating mode is unchanged.
Warning code Communication error CIMxxx is
displayed in Grundfos GO Remote.
The CIM module is unable to communicate with
the product.
Cause
The CIM module is installed
incorrectly.
Remedy
Ensure that the module,
including cables, is fitted
correctly.
Cause
The CIM module is defective.
Remedy
Contact Grundfos.
Related information
2.2.4 Installing a communication interface module
26
8.19 Code 163 (Drive unit configuration
fault)
Alarm code 163 is shown on the display.
The alarm symbol on the display turns red, but
the pump's operating mode is unchanged.
Alarm code Drive unit configuration fault is
displayed in Grundfos GO Remote.
Cause
The configuration of the motor-
drive unit is incorrect.
Remedy
Reconfigure the phase setting
on the unit using Grundfos GO
Remote.

8.20 Code 165 (Signal fault)

Alarm code 165 is shown on the display.
The alarm symbol on the display turns red and
the pump stops.
Alarm code Signal fault is displayed in Grundfos
GO Remote.
Cause
The signal from the sensor is
out of the configured range.
Remedy
Go to Settings > Level
Control in Grundfos GO
Remote and ensure that the
configured range corresponds
to the physical application
type.
Change the sensor, if needed.

8.21 Code 191 (High water level)

Alarm code 191 is shown on the display.
The alarm symbol on the display turns red, but
the pump's operating mode is unchanged.
Alarm code High water level is displayed in
Grundfos GO Remote.
Cause
The defined start level did not
start the pump.
Remedy
Check and configure the
sensor for start level.
Cause
The pump is not big enough to
remove the water.
Remedy
Contact Grundfos or an
authorised service workshop.
Cause
The level sensor is defective and
not reacting on level changes.
Remedy
Check the functionality of the
level sensor.