1.
Press and hold OK until the display and dry
running start flashing.
2.
Continuously press OK until the indicator light for
the start level for pump 1 starts flashing.
3.
Set the start level for pump 1 by using
the Up and Down buttons.
4.
Continuously press OK until the display stops
flashing.
The settings have now been stored.
6.4 Setting the stop level
6.4.1 Setting the stop level with Grundfos GO
Remote
The settings apply to analog sensors. For digital
sensors, the setting is automatically activated.
1.
Go to Settings > Level control > Stop level
2.
Set the stop level.
If you are using the same level for
start and stop, remember to set a stop
delay. This will prevent the pump from
starting and stopping too frequently.
6.4.2 Setting the stop level with the operating
panel
The settings apply to analog sensors. For digital
sensors, the setting is automatically activated.
1.
Press and hold OK until the display starts
flashing.
2.
Press OK once.
The current stop level is indicated on the display.
3.
Set the stop level using
the Up and Down buttons.
4.
Continuously press OK to confirm all other
settings and to exit the setup.
16
If you are using the same level for the
start and stop level, remember to set
a stop delay. This will prevent the
pump from starting and stopping too
frequently.
6.5 Setting the high level
6.5.1 Setting the high level with Grundfos GO
Remote
For analog sensors:
1.
Go to Settings > Level control > High level.
2.
Set the high level.
For digital sensors:
1.
Go to Settings > LC 231 IO terminals
2.
Select which terminal to configure.
6.5.2 Setting the high level with the operating
panel
The settings apply to analog sensors
1.
Press and hold OK until the display starts
flashing.
2.
Press OK four times. The current high level is
indicated on the display.
3.
Set the high level using
the Up and Down button.
For digital sensors, enable or disable the setting.
1.
Press OK once to complete the setting.
6.6 Stop delay
The stop delay is the time from when the stop level is
reached until the pump stops. The stop delay
prevents the pump from starting and stopping too
frequently and reduces water hammer in long pipes.
6.6.1 Setting the stop delay with Grundfos GO
Remote
1.
Select Settings > Level control > Stop delay >
State
2.
Select Stop delay time.
3.
Set the Stop delay time.
6.7 Power-on delay
With this function it is possible to delay the startup of
the pump after the power supply has been switched
on. The purpose is to avoid disturbing the main power
network which could happen if several pumps start up
immediately when the power supply is switched on.
6.7.1 Setting the power-on delay with Grundfos
GO Remote
1.
Go to Settings > Power-on delay.
2.
Set the function to Enabled.
3.
Set the time delay.