ADMC INSTALLATION

DETERMINE LOCATION FOR CONTROL

The Model 5558 Automatic Digital Modulating Control (ADMC) should
be installed in the space being humidified in order to control moisture
levels . See FIGURE 14 .
Do not mount ADMC:
• In the flow of a supply register or near the outlet of the Steam
Humidifier Fan Pack .
• Behind doors, in corners, or other dead air spaces .
• In direct sunlight, near lighting fixtures, or other appliances that give
off heat .
• On an outside or unconditioned area wall .
• In stairwells or near outside doors .
• On a wall with concealed pipes or ductwork .
CAUTION
RISK OF DAMAGE. Disconnect power to humidistat prior to
separating humidistat from its base.
1. Loosen the bottom screw holding the front cover to the base .
2. Lift the front cover of the humidistat to separate it from the base .
3. Pull wires through the base hole .
4. Secure the base to the wall using wall anchors and screws
(provided) .
5. Wire the control . See ADMC WIRING on page 14 .
6. Install the humidistat to the base and tighten the bottom screw .

TERMINAL DESCRIPTIONS

1
Common
2
24VAC
6
Not Used
7
Relay Common
8
Humidify dry or powered contact (see JUMPER SETTINGS)
9
Dehumidify dry contact (NOT USED)
10
Humidify set point analog output (NOT USED)
FIGURE 14 – MOUNTING LOCATION
18"
MINIMUM
NO
NO
11
Alarm status digital input (NOT USED)
12
External humidity sensor
13
Outdoor temperature sensor
14
Humidify Modulating output
15
Dehumidify Modulating output (NOT USED)
16
Actual humidity output (NOT USED)
NO
5
FEET
90-1666
English 13