ADMC TECHNICAL DATA
Outputs
Inputs
Power supply
Power consumption
Set point range
Sensor precision
Proportional band
Electrical connection
Operating condition
Storage condition
Temperature compensation reset feature
Weight
ADMC DIMENSIONS
Dimension
Imperial (inches)
A
2 . 8 5
B
4 . 8 5
C
1 . 0 0
D
2 . 3 6
E
3 . 2 7
Actual humidity (0-100%RH), 0-10 Vdc / 2-10 Vdc
Humidity set point (0-100%RH), 0-10 Vdc / 2-10 Vdc
Humidification proportional control signal, 0-10 Vdc / 2-10 Vdc
Dehumidification proportional control signal, 0-10 Vdc / 2-10 Vdc
Humidification dry contracts 24 Vac, 1 A max, 3 A in-rush
Dehumidification dry contracts 24 Vac, 1 A max, 3 A in-rush
Window temperature sensor or outside temperature sensor (10 K )
External humidity sensor (0-10 Vdc / 2-10 Vdc) or high limit (0-10 Vdc / 2-10 Vdc)
1 alarm status digital input (24 Vac or dry contact)
22 to 26 Vac 50/60 Hz or 28 to 32 Vdc
1 VA
10 - 90%RH (in 1% increments)
± 3% or better at 40%RH and 23°C (73°F)
2% to 10% for control signal
0 . 8 mm2 (18 AWG) minimum
0°C to 40°C (32°F to 104°F), 0-95%RH
-10°C to 50°C (14°F to 122°F), 0-95%RH
Automatic readjustment of set point from an Outdoor Temperature Sensor (included)
130 g (0 . 3 lb)
Metric (mm)
73
123
B
24
60
83
E
D
A
C
English 31