INSTALLATION INSTRUCTIONS

LOCATION

The Fan Pack must be located near the Steam Humidifier to minimize
the length of the steam hose . If the Fan Pack is mounted directly above
the humidifier, at least 6" is required for the steam hose to make the
bend . See FIGURES 4-6 for installation options .
Six feet of steam hose is provided with the Steam Humidifier . For
installations that require longer runs, a combination of the steam hose
and insulated copper pipe can be used . See FIGURE 6 . When using
more than 24" of steam hose or 36" of insulated copper pipe, install
a Drain Tee and Trap (#4028) to help control condensate and reduce
gurgling . See FIGURE 6 .
Due to condensation inside the hose or pipe, the output of the Fan Pack
depends on the length of the steam hose or pipe connecting it to the
Steam Humidifier .
To prevent condensation on surfaces and furnishings, install the Fan
Pack so the steam being discharged has enough room to be absorbed
into the air before encountering surfaces .
FIGURE 5 – SIDE VIEW
TYPICAL INSTALLATION
16" MINIMUM
FOR STEAM HOSE
30" RECOMMENDED
FOR SERVICE ACCESS
STEAM HUMIDIFIER
6 English
FIGURE 4 – EXTERNAL FAN PACK INSTALLATION
FIGURE 6
FAN PACK
STAINLESS STEEL
45° ELBOW
90-2194
FAN PACK
6" MINIMUM
FOR STEAM HOSE
30" RECOMMENDED
FOR SERVICE ACCESS
STEAM HUMIDIFIER
3/4" x 1-1/4"
REDUCING COUPLER
SERVICE PART #4028
(INCLUDING CLAMPS)
TO DRAIN
90-2347
FAN PACK
STEAM HOSE
3/4" x 1-1/4"
REDUCING COUPLER
1" COPPER INSULATED
STEAM HOSE
STEAM HUMIDIFIER
90-2022