HUMIDIFIER LOCATION

Do not mount humidifier in a location where operating ambient
temperature exceeds 140°F or where freezing temperatures may
occur. Extreme temperatures may cause the humidifier to leak which
can cause damage .
Mount humidifier in a location that allows access for servicing, and
clearance to remove front panel for replacing the canister and side
panel for access to the electrical components during installation . See
FIGURE 11 for minimum clearances around humidifier .
The humidifier should be mounted as close to the Fan Pack as possible .
Allow a minimum of 2" of steam hose to extend straight out of the
humidifier before beginning any bends; this will help ensure a tight
connection with the top of the canister .
Mount the humidifier to a structurally stable surface that can bear the
full load of the humidifier .
The humidifier must be mounted to a vertical surface and must be
mounted level in the upright position .

PREPARE HUMIDIFIER FOR MOUNTING

Unpack carton . Open front panel by removing screw and lifting panel up and away from humidifier . Disconnect three wires from top of canister
by pulling straight up . The two large wires are the electrode conductors . The smaller wire is connected to the high water level sensor . Remove
canister by pulling it up and out of drain assembly . Remove two screws on right side of humidifier and lift side panel off housing to expose electrical
compartment .

INSTALL FAN PACK

Make sure the Fan Pack is mounted higher than the humidifier so that condensation that forms in the steam hose runs back into the canister .

MOUNT HUMIDIFIER

Secure humidifier to a sturdy wall using screws provided, or to sheet metal duct . Humidifier initially weighs 23 lbs with a full canister, but will increase
in weight over time due to the precipitation of minerals inside the canister . Make sure mounting system will support weight . If mounting to stud frame
wall, install two spanner boards to studs and fasten humidifier to spanner boards . Make sure humidifier is mounted plumb .

INSTALL STEAM HOSE

Six feet of steam hose is provided with the humidifier . If the steam hose must be cut, use a hacksaw . If additional length is required, use 1" O . D . metal
or copper pipe . Do not use PVC pipe for steam line. Insulate pipe with 1" thick insulation rated for 212°F or higher to reduce steam loss .
Use the steam hose provided . Other hoses may have impurities which can cause foaming in the canister . Foaming can cause water level inaccuracies,
reduced steam production and water sputtering from the Fan Pack . When using pipe, remove all traces of residual materials used to connect the pipe
to prevent foaming .
Verify that the O-ring is in place in the groove in the drain assembly .
Attach steam hose to dispersion tube and then to top of canister using hose clamps provided . Make sure steam hose has a constant slope of at least
2" per foot between the dispersion tube and the humidifier . Support the steam hose in multiple locations over its span to prevent sagging .
Attach and fully seat the electrode conductors (interchangeable) and the high water level sensor wire to the top of the canister .
FIGURE 11 – CLEARANCES
FRONT VIEW
16" FOR
ELECTRICAL
ACCESS
4"
16"
FOR DRAIN
SIDE VIEW
30" FOR
SERVICE
ACCESS
90-1519