PROGRAM MODE
To enter program mode for ADMC set up, remove the humidistat from its base . On the ADMC back, place Jumper J3 in the PGM position then reinstall
onto the base . The symbol
will be displayed . Press button
value, press button
to return to preceding stage . Exit the programming mode at any time by placing Jumper J3 in the RUN position, settings
will be saved . JUMPER J3 MUST BE IN RUN MODE TO OPERATE.
Step
Display
Description
Internal humidity sensor offset calibration:
Display shows
humidity percentage read by internal humidity sensor and the Humidify symbol
1
is displayed .
You can adjust the calibration of the sensor by comparing with a known
humidistat .
Internal temperature sensor calibration:
Display shows
read by internal temperature sensor .
2
You can adjust the calibration of the sensor by comparing with a known
thermometer .
Minimum set point:
Display shows
humidity set point .
3
Select the desired minimum humidity set point .
The minimum set point is restricted by the maximum value . (Step 4)
Maximum set point:
Display shows
humidity set point .
4
Select the desired maximum humidity set point .
The maximum set point is restricted by the minimum value . (Step 3)
Locking the set point:
Display shows
The set point adjustment can be locked or unlocked . If locked,
5
symbol will appear, and set point adjustment will not be allowed in the operating
mode .
20 English
to advance to the next program function, press buttons
inside humidty sensor offset
inside temper sensor offset
adjust minimum user setpnt
adjust maximum user setpnt
user setpnt locked
and the status of the function .
Values
Range: 10 to 90%RH
and the relative
Increment: 0 . 1 %RH
0 . 0 %RH no humidity sensor
(factory calibrated)
Range: 50 to 104°F
and the temperature
Increment: 0 . 2 °F [0 . 1 °C]
(factory calibrated)
Minimum range: 10 to 90%RH
and the minimum
Increment: 1%RH
Default setting: 15%RH
Maximum range: 10 to 90%RH
Increment: 1%RH
and the maximum
Default setting: 65%RH
yes
and Lock
Default setting: Unlocked (NO)
or
to change
(max . offset ± 5%)
[10 to 40°C]
(max . offset ± 5°C)