MarelliMotori D-Vo Light Manual Del Usuario página 51

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

FCR
FCR physical contact open
No action performed.
NOTE: if the auxiliary power supply is missing, the STOP state information is lost; as a consequence, the START
and STOP management and the relevant LED state only apply when the D-Vo is running under one of the following
operating conditions:
1. separate power and auxiliary supply, i.e. auxiliary supply always on even when the generator is stopped;
2. auxiliary supply shunted from power supply and generator running at full rpm (with residual auxiliary supply
>20Vac).
Monitor
The Monitor windows provides the real-time values of the quantities monitored by D-Vo.
MONITORED QUANTITIES
Generator voltage UV
Generator voltage VW
Generator voltage WU
Generator average voltage
Generator current U
Generator current V
Generator current W
Generator average current
Generator frequency
Exciter field voltage
Exciter field current
Exciter field current ripple
Grid voltage UV
Grid frequency
Apparent power
Real power
Reactive power
Power factor
Input E1+/E1- (4~20mA)
Input E2+/E2- (4~20mA)
Input V+/V- (+/-10V)
Internal bus DC voltage
Alarms/Warnings
The Alarms/Warnings window provides information on any alarm or warning states triggered by abnormal operating
conditions of the generator.
9638571A0_C
FCR physical contact closed
D-Vo is operating in FCR regulation mode
(manual excitation control).
UM
[V]
[V]
[V]
[V]
[A]
[A]
[A]
[A]
[Hz]
[V]
[A]
[%]
[V]
[Hz]
[kVA]
[kW]
[kVAR]
[mA]
[mA]
[V]
[V]
D-Vo Light – Marelli Motori
7
EN
8
51

Publicidad

Tabla de contenido
loading

Tabla de contenido