Auto-coupling base installation on a plinth
The minimum required plinth heights (A) for installation on auto
coupling are indicated in the following table.
Pump type
Range 72
S2.35.A100.xxxx.x.x
S2.40.A100.xxxx.x.x
S2.40.A120.xxxx.x.x
S3.40.A120.xxxx.x.x
S3.45.A200.xxxx.x.x
S3.50.A200.xxxx.x.x
Range 74
S2.40.xx.xxx.xxxx.x.x
S3.40.xxx.xxx.xxxx.x.x
S3.45.xxx.xxx.xxxx.x.x
S3.50.xxx.xxx.xxxx.x.x
Range 78
S3.xx.xxx.xxx.xxxx.x.x
S4.xx.xxx.xxx.xxxx.x.x
14
Minimum plinth height (A)
[in (mm)]
17 (431)
15.75 (400)
16.75 (425)
15.75 (400)
16.75 (425)
16.75 (425)
Lowering the pump onto an auto coupling
Required tilt angle when the pump is lowered onto the auto
coupling: 5 ° ± 5 °
Submerged installation on auto coupling
Pumps for permanent installation can be installed on a stationary
auto coupling and operated completely or partially submerged in the
pumped liquid.
Before installing the auto-coupling base unit, ensure the quality and
strength of the concrete foundation. See the pull-out strengths
required for anchor bolts at the end of this section. To ensure
adequate pull-out strength, weld the threaded bushings to the steel
reinforcement in the concrete.
For auto-coupling installations, types S (submerged
without cooling jacket) and C (submerged with cooling
jacket), the guide claw is mounted on the outlet flange
from factory.