NOTE: The gas service to a gas dryer must conform
with the local codes and ordinances, or in the
absence of local codes and ordinances, with the
latest edition of the National Fuel Gas Code ANSI
Z223.1/NFPA 54 or the CAN/CGA-B149, National
Gas Installation Code.
Natural Gas, 1,000 Btu/ft
be supplied at 6.5 ± 1.5 inch water column pressure.
For proper operation at altitudes above 2,500 feet (760
m) the natural gas valve spud orifice size must be
reduced to ensure complete combustion. See table at
right.
L.P. (Propane) Gas, 2,500 Btu/ft
service must be supplied at 10 ± 1.5 inch water column
pressure.
NOTE: DO NOT connect the dryer to L.P.
(Propane) Gas Service without converting the gas
valve. An LPK1 Sales Accessory (L.P. [Propane]
Gas Conversion Kit 649P3) must be installed.)
NOTE: The dryer and its appliance main gas valve
must be disconnected from the gas supply piping
system during any pressure testing of that system at
test pressures in excess of 1/2 psi (3.45 kPa). (See
illustration on page 10.)
The dryer must be isolated from the gas supply piping
system by closing the equipment shut-off valve during
any pressure testing of the gas supply piping system at
test pressures equal to or less than
1/2 psi (3.45 kPa)
NOTE: When connecting to a gas line, an
equipment shutoff valve must be installed within 6'
(1.8 m) of the dryer. An 1/8" N.P.T. pipe plug must
be installed as shown. See illustration.
STAINLESS
STEEL
FLEXIBLE
CONNECTOR
USE ONLY
IF ALLOWED
BY LOCAL
CODES
Design A.G.A.
Certified
Connector)
GAS CONNECTION
16
Gas Requirements . . .
(Gas Dryers)
3
3
(37.3 MJ/m
) service must
3
3
(93.1 MJ/m
)
NEW
(Use
3/8" NPT
BLACK IRON PIPE
Shorter than 20' (6.1 m) - use 3/8" pipe
Longer than 20' (6.1 m) - use 1/2" pipe
WARNING
To reduce the risk of gas leaks, fire or
explosion:
• The dryer must be connected to the type
of gas as shown on nameplate located in
the door recess.
• Use a new flexible stainless steel
connector.
• Use pipe joint compound insoluble in LP
(propane) Gas, or Teflon tape, on all pipe
threads.
• Purge air and sediment from gas supply
line before connecting it to the dryer.
Before tightening the connection, purge
remaining air from gas line to dryer until
odor of gas is detected. This step is
required to prevent gas valve
contamination.
• Do not use an open flame to check for gas
leaks. Use a non-corrosive leak detection
fluid.
Altitude
Orifice Size
ft
m
#
3000
915
43
6000
1830
44
8000
2440
45
9000
2740
46
10000
3050
47
1/8" NPT
PIPE PLUG
(For checking
inlet gas pressure)
EQUIPMENT
SHUT-OFF
VALVE
Installed within
6' (1.8 m) of dryer
W114R1
Part
Number
Inches
mm
0.0890
2.26
503778
0.0860
2.18
58719
0.0820
2.08
503779
0.0810
2.06
503780
0.0785
1.99
503781
D233IE2E
504607