■ K Type
10-9. Caution
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor
unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4).
* If multiple indoor units are used, also refer to "10-16. System Control".
The indoor and outdoor unit control PCB utilizes a semiconductor memory element (EEPROM). The set-
tings required for operation were made at the time of shipment.
Only the correct combinations of indoor and outdoor units can be used.
10-10. Test Run Procedure
Turn ON the indoor
and outdoor power.
(Automatic Address setting)
DC̲Inverter̲Eng.indd 75
DC̲Inverter̲Eng.indd 75
Recheck the items to check before the test run.
Check the combination (wiring) of indoor and
outdoor units.
Is system "single-type"?
YES
(1 indoor unit is connected
to 1 outdoor unit)
Are multiple outdoor units used?
Turn ON the indoor and outdoor power.
(Automatic Address Setting)
Set the indoor unit control switch to "TEST".
Can
operation be
started?
Slide the indoor unit control switch back to "ON".
(See 10-11)
(See 10-16)
NO
YES
(See 10-16-2) In case of group control
NO
(See 10-13)
Refer to "Table of Self-Diagnostic
NO
Functions" to check the system.
In addition, refer to 10-16 and
correct any items that need to be
corrected.
YES
Note: Check the indoor-side drainage.
(See 10-13)
Fig. 10-9
75
Confirm wiring is done
in accordance with
Fig. 2, " Basic Wiring ".
(See 10-16-3 to 10-16-6)
How to Set Automatic Address
Set the automatic
address setting from
outside unit.
(See 10-15)
2007/07/25 13:21:50
2007/07/25 13:21:50
GB
FR
DE
IT
PT
GR
ES