1.6 MALFUNCTIONING OF THE UNIT AND ERROR CODES 
When an error occurs or the protection mode is set automatically, the circuit board and the wired controller will both display the 
error message. 
Protection/ 
Error code 
Malfunction 
Standby 
Normal running 
Lower tank water 
temp. sensor failure  
Upper tank water 
temp. sensor failure 
Evaporator coil 
temp. sensor failure 
Return gas temp 
sensor failure  
Ambient temp. 
sensor failure 
Hot Sanitary / Solar 
temp. sensor failure 
Situation of remote 
on/off signal 
T6 too high 
temp.protection 
High pressure 
protection (HP 
Switch) 
Low pressure 
protection (LP Switch) 
Over heat protection 
(T85°C Switch)  
Flow switch 
Defrosting 
Defrost  
indicate 
Communication 
failure 
 
 
 
LED indicator 
 
Dark 
 
Bright 
● 
P1 
(1flash 1 dark) 
☆☆
● 
P2 
(2 flashes 1 dark) 
☆☆☆
● 
P3 
(3 flashes 1 dark) 
☆☆☆☆
● 
P4 
(4 flashes 1 dark) 
☆☆☆☆☆
● 
P5 
(5 flashes 1 dark) 
P6 
Dark 
P7 
Dark 
P8 
Dark 
☆☆☆☆☆☆
● 
E1 
(6 flashes 1 dark) 
☆☆☆☆☆☆☆
E2 
(7 flashes 1 dark) 
☆☆☆☆☆☆☆☆
E3 
(8 flashes 1 dark) 
☆☆☆☆☆☆☆☆☆
E5 
(9 flashes 1 dark) 
☆☆☆☆☆☆☆☆
(all long flashes) 
E8 
Bright 
Possible reasons 
 
 
1) The sensor open circuit 
2) The sensor short circuit 
1) The sensor open circuit 
2) The sensor short circuit 
1) The sensor open circuit 
2) The sensor short circuit 
1) The sensor open circuit 
2) The sensor short circuit 
1) The sensor open circuit 
2) The sensor short circuit 
1) The sensor open circuit
2) The sensor short circuit 
When remote signal is on, no P7 
will be showed on the controller, 
when remote signal is off, P7 will 
be displayed. It is not an error 
code, but a situation for remote 
on/off signal. 
1) T6 too high temp. 
2) T6 sensor has problem 
1) Too high air inlet temp 
2) Less water in the tank 
3) The electronic expansion valve 
assembly blocked 
4) Too much refrigerant 
5) The HP switch damaged 
6) The uncompressed gas is in 
refrigerant system 
1) Too low air inlet temp 
2) The electronic expansion valve 
● 
assembly blocked 
3) Too less refrigerant 
4) The LP switch damaged 
5) The fan assembly can not work 
● 
1) Too high tank water temp 
2) The T85°C switch damaged 
No water flow detected: 
1) Pump not powered 
● 
2) Pump malfunction 
3) Dirty water filter 
4) Flow switch malfunction 
 
 
Corrective actions 
 
 
1) Check the sensor connection 
2) Replace the sensor 
1) Check the sensor connection 
2) Replace the sensor 
1) Check the sensor connection 
2) Replace the sensor 
1) Check the sensor connection 
2) Replace the sensor 
1) Check the sensor connection 
2) Replace the sensor 
1) Check the sensor connection
2) Replace the sensor 
 
1) P8 appears at 125°C and disappears at 
120°C 
2) Check and if it's necessary replace the 
sensor 
1) Check if the air inlet temp is over the 
working limit 
2) Check if the tank is full of water. If not, 
charge water 
3) Replace the electronic expansion valve 
assembly 
4) Discharge some refrigerant 
5) Replace a new switch 
6) Discharge and then recharge the refrigerant 
1) Check if the air inlet temp is over the 
working limit 
2) Replace the electronic expansion valve 
assembly 
3) Charge some refrigerant 
4) Replace a new switch 
5) Check if the fan working when the 
compressor working. If not, some problems 
with the fan assembly 
1) If the tank water temp is over 85°C, the 
switch will open and the e‐heater will stop for 
protection. After the water comes to normal 
temp, the protection is auto‐reset 
2) Replace a new switch  
1) Check pump power supply
2) Verify pump electrical connections and 
pump rotation. If necessary replace the 
pump 
3) Clean the filter 
4) Check the flow switch contacts and 
functioning 
 
 
21