2 MAINTENANCE AND PERIODICAL CONTROLS 
WARNING:  All  the  operations  described  in  this  chapter  HAVE  TO  BE  CARRIED  OUT  BY  TRAINED  STAFF  ONLY. 
Before  any  operation  or  before  entering  the  inner  components  of  the  unit,  be  sure  that  the  power  supply  is 
disconnected. The compressor's head and discharge piping are usually at high temperature levels. Be very careful 
when operating in their surroundings. Aluminium coil fins are very sharp and can cause serious wounds. Be very 
careful when operating in their surroundings. After maintenance operations, re‐install the cover panels, and fix 
 
them by means of screws where necessary. 
WARNING: The unit should be installed so that adequate clearance is available for maintenance and repairation. 
The warranty does not cover costs related to platforms or handling equipment necessary for any maintenance. 
The refrigerant circuits must not be filled with different gas other than that indicated on the nameplate. The use 
of a different refrigerant can cause severe damage to the compressor. 
It's  forbidden  to  use  oils  other  than  those  specified in  this  manual.  The  use  of  a  different  oil  can  cause  serious 
 
damage to the compressor. 
It is recommended to set a lower temperature to decrease the heat release, prevent scale and save energy if the 
outlet water is sufficient. 
 
It is a good rule to carry out periodic checks in order to verify the proper operation of the unit: 
OPERATION 
Check the water supply and air vent frequently, to avoid lack of water or air in the water loop. 
Check out that safety and control devices work correctly. 
Check out possible oil leakage from compressor. 
Check out possible water leakages from the hydraulic circuit. 
Check out the proper working of the external flow switch (if it is installed). 
Clean  the  metallic  filters  of  the  hydraulic  circuit
water can damage the unit. 
Clean the finned coil of the heat exchanger by means of compressed air (it's recommended to
unit in a place where it is dry and clean, and which has good ventilation). 
Check out that all the terminals on the electric board as well as on the terminals of the compressor are 
properly fixed. 
Make  sure  the  electrical  components  are  good.  If  there  is  a  damaged  part  or  a  strange  smell,  please 
replace it in time. 
Tightening of water connections. 
Keep the unit clean by means of soft damp cloth. 
It is recommended to clean the tank and e‐heater regularly to keep an efficient performance.
Clean any external air filter regularly to keep an efficient performance.
Correct voltage. 
Correct absorption. 
Check each part of the unit and the pressure of the system. Replace the defect part if there is  any, and 
recharge the refrigerant if it is required. 
Check the operating pressure, and superheat and subcooling
Check of the efficiency of circulation pump. 
If the heat pump is not used for a long time, please drain out all the water from the unit and seal the unit 
to  keep  it  good.  Please  drain  the  water  from  the  lowest  point  of  the  boiler  to  avoid  freezing  in  winter. 
Water recharge and full inspection on the heat pump is required before it is restarted. 
Check and if necessary replace the magnesium stick. 
2.1 ENVIRONMENTAL PROTECTION 
According  to  the  norms  dealing  with  the  use  of  depleting  stratospheric  ozone  substances,  it  is  forbidden  to  release  refrigerants 
fluids  in  the  atmosphere.  They  have  to  be  collected  and  delivered  to  the  seller  or  to  proper  gathering  points  at  the end  of  their 
operating  life.  Refrigerant  R134A  is  mentioned  among  controlled  substances  and  for  this  reason  it  has  to  be  subjected  to  the 
mentioned  norms.  A  particular  care  is  recommended  during  service  operations  in  order  to  reduce  as  much  as  possible  any 
refrigerant loss. 
This equipment contains R134a refrigerant in the amount as stated in the specification. Do not vent R134a into 
the atmosphere: R134a, is a fluorinated greenhouse gas with a Global Warming Potential (GWP) = 1300. 
 
It should only be serviced or dismantled by professional trained personnel. 
3 TROUBLESHOOTING 
This  section  provides  useful  information  for  diagnosing  and  correcting  certain  troubles  which  may  occur.  Before  starting  the 
troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections 
22
 
 
to  keep  a  good  water  quality.  Lack  of  water  and  dirty 
1 month 
4 months 
 
keep the 
 
 
 
 
 
 
 
 
 
 
 
 
 
6 months 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
x
x
x
x
x
x
 
x
x
 
 
every year