C4 Close after leaving the photo cell, 000..0.019, 0.5
s
C5 EMERGENCY stop input
000= automatic closing after EMERGENCY STOP
locked
001= closing time starts again after release
EMERGENCY stop
C6 Function connections
Connection 3
000
STOP
STOP
001
STOP
STOP
002
STOP
STOP
003
OPEN
CLOSE
Stop
STOP
C7 PARKING ASSISTANT operator light flashes
when door can be closed
000= OFF 001= ON
(only in connection with photo cell)
1)
If the added load (A5, A6) is >003 and/or the
automatic closing (b4, c1) is set to ON (>000), the door
may only be operated with an additional safety device.
WARNING: to ensure that the closing force value comply with
limits established by the EN 12453 standard für door models
Basematic 42, Superior 42/+42/+42 WIDE with pass door,
Secura with pass door, Comfort with pass door and SSD, the
following parameters values must be set: A1 = 008; A2 = 003
and A6 = 000. This operation must be performed only by
qualified personnel.
19 Reset
ATTENTION: There is no longer any protection by
switching off the load after the reset. Teach the
door operator in again before re-commissioning. For this
carry out
Teaching in the door operator (Chapter 15) .
Reset (saved values of the teach-in runs)
Press and hold buttons
and menu
during one of the 3 status messages A, B or C (see
Chapter 10). The indicator lamp (rES) flashes after a few
seconds then L4 is displayed and the reset is made.
The remote transmitters are not deleted.
Reset, factory setting
• Pull out plug (1, green).
• During one of the 3 status messages A, B or C (see 10)
press the pushbuttons
longer than 12 seconds. The display flashes slowly at first,
then quicker (rES). Then the status display reappears, the
reset is made.
The values shown under Programming (Chapter 18) are
set. The remote transmitters are not reset.
20 Attaching additional safety devices
Photo cell
Function: When the safety input is activated (opening the
contact) the operator stops and reverses as far as the OPEN
end position.
Magic 1000-2
Connection 4
Partial opening
STOP
STOP
STOP
STOP
simultaneously
and Menu
simultaneously for
If the "automatic closure" function is also activated, following
000
the third successive obstruction message, the operator will
move to the OPEN end position and shut down.
000
Connection: Pull out plug with yellow bridge on the external
junction 2 and store it. Plug on safety device.
000
Safety edge, opto-sensor
connected by extension modules.
EMERGENCY stop
Function: If the external safety device is operated when the
door is moving (Contact opened), the door stops immediately.
Once the EMERGENCY stop contact has closed, the door
operator can be moved again with the next pulse.
Connection: Pull out plug with green bridge on the external
junction 5 and store it. Plug on safety device.
000
21 Additional connections
Additional lighting
Connection must be performed only by qualified electricians.
In addition to the operator light (5 W LED lamp), optional
lighting of a maximum of 60 W (no tubular fluorescent lamps)
can be connected to terminals 1 and 2.
Note: Some energy-saving lamps can interfere with the radio
signal.
External pulse input
An external pulse signal (e.g. wall button) can be connected
to terminals 14 and 15. Fixed control devices like buttons or
similar should be installed at a height of at least 1,5 m and
within sight of the door but away from moving parts. Key
actuated switches can be installed at lower height.
Additional antenna
An external antenna can be connected to terminals 17 and 16
(GND). The internal antenna (terminal 17) must be
disconnected.
16
15
17
Figure: Control board See also page 219.
22 Troubleshooting
Interference frequencies
The wireless signals of other 868 MHz transmitters can
interfere with the door operator.
Self-test
The system runs a self-test after initialisation, after each
motor operation and after every 2.25 hours in idle mode.
Error free = status message.