Activation via break-glass point: Break the glass cover
and press the red button for at least 1 second. The window opens. (The
comfort ventilation function is automatically disengaged).
signals: The red light-emitting diodes of the control system and the
connected break-glass points are illuminated. In addition, the acoustic
alarm from control system and connected break-glass points sounds
continuously.
resetting after activation via break-glass point: Open the door of
control system or break-glass point in question. Press the reset button in
the control system or the break-glass point. The window closes and con-
trol system and connected break-glass points are reset. After activation
of the reset button, the comfort ventilation and the smoke ventilation
are operational again.
signals: When the reset button has been activated, the red light-emit-
ting diodes of the control system and the connected break-glass points
are turned off and the alarm signal stops.
release via smoke detector: In cases of smoke detection, the window
opens automatically. The comfort ventilation function is automatically
disengaged. If the smoke ventilation system is activated via smoke
detector, the smoke detector has to be cleared of smoke particles or
replaced before the reset button is activated.
signals: The red light-emitting diode in the control system, in the smoke
detector and in the connected break-glass points are illuminated. In
addition, the acoustic alarm from control system and connected break-
glass points sounds continuously.
release by high temperatures: If the temperature in the control sys-
tem rises above 70°C, the window opens automatically.
signals: The red light-emitting diode in control system and connected
break-glass points is illuminated. The yellow light-emitting diode for
error indication in control system and connected break-glass points
flashes on and off.
resetting after release by high temperatures: Close the window
again by one press of the reset button in the control system.
signals: After activation of the reset button, the yellow light-emitting
diode for error indication keeps flashing on and off in the connected
break-glass points. The green light-emitting diode remains illuminated
as the built-in thermal cut-out is irreversibly destroyed. Therefore the
entire printed circuit board must be replaced.