8.10 Priority of settings

The external forced-control signals influence the settings
available on the pump operating panel or with Grundfos GO.
However, you can always set the pump to maximum-curve duty or
stop the pump on the operating panel or with Grundfos GO.
If two or more functions are enabled at the same time, the pump
operates according to the setting with the highest priority.
The priority of the settings is as shown in the table below.
Example: If the pump has been forced to stop via an external
signal, the operating panel or Grundfos GO can only set the pump
to maximum curve.
Possible settings
Operating
Priority
panel or
Grundfos GO
1
"Stop"
2
"Max. curve"
3
4
5
6
7
8
9
"Min. curve"
10
11
"Start"
External
Bus signal
signals
"Stop"
"Stop"
"Max. curve"
"Min. curve"
"Start"
"Max. curve"
"Min. curve"

8.11 Input and output communication

Relay outputs
Alarm, ready and operating indication via signal relay.
Digital input
– Start and stop (S/S)
– Minimum curve (MI)
– Maximum curve (MA).
Analog input
0-10 V or 4-20 mA control signal.
To be used for external control of the pump or as sensor input
for the control of the external setpoint.
The 24-V supply from pump to sensor is optional and is
normally used when an external supply is not available.
WARNING
Electric shock
Death or serious personal injury
- Separate input voltages from external equipment
from live parts by reinforced insulation.

8.11.1 External connections in a multipump system

The following external connections need only to be fitted to the
master pump:
analog input
digital input
communication interface module, CIM
If you want to monitor a slave pump, mount a communication
interface module on the slave pump too.
The following external connections need to be fitted on both the
master and slave pumps:
Relays (from model B)
The following are system parameters shared between the pumps:
Operating mode, control mode and setpoint
Heat energy monitor:
Both pumps display the heat energy for the entire system and
not only for the individual pump. Please note that all
calculations are made in the master pump. If the master pump
loses power, the heat energy will cease to increment. See also
section 8.11.5 Heat energy monitor.
For more information about input and output communication in
multipump systems, see sections 8.11.2 Relay outputs,
8.11.3 Digital inputs and 8.11.4 Analog input.