Installation

Location Requirements

The location selected for the ice machine head section must
meet the following criteria. If any of these criteria are not
met, select another location.
• The location must be indoors and must be free of
airborne and other contaminants.
• The location must not be near heat-generating
equipment or in direct sunlight.
• The location must allow enough clearance for water,
drain, and electrical connections in the rear of the ice
machine.
• The location must not obstruct airflow through or around
the ice machine.

Installation Requirements

• The ice machine and bin must be level.
• Vent the ice machine and bin drains separately.
• Bin drain termination must have an air gap.
• The ice machine and bin must be sanitized after
installation.
• The drain line must contain a union or other suitable
means of disconnection at the ice machine.
QuietQube Models Only
• The ice machine top panel can be trimmed with an
aviator snips to allow the line set, water line and
electrical connections to exit the top. Only cut out what is
needed, the back panel must support the top panel.
• The water inlet and electrical connection must contain a
service loop to allow future access.
Part Number: 000013325 Rev 02 6/17
Section 2
Installation
Minimum/Maximum Temperatures
Model
All Ice Machine Head Sections
All Remote Condensers
QuietQube Condensing Units
ICVD0695 - ICVD0696
ICVD1195 - ICVD1196
ICVD2095 - ICVD2196
ICVD0895 - ICVD0896
ICVD0996
ICVD1095 - ICVD1096
ICVD1495 - ICVD1496
ICVD1895 - ICVD1896

Ice Machine Heat of Rejection

Ice Machine
Series
I0300
I0320
I0450
I0500
I0520
I0600
I0850
I0906
I1000
I1200
I1400
I1800
I3300
Use this information when:
• Sizing air conditioning equipment where self-contained
air-cooled ice machines are installed.
• Determining the load on a cooling tower – Use the peak
figure for sizing the load.
Minimum Air
Maximum Air
Temperature
Temperature
2°C
35°F
-29°C
-20°F
-29°C
-20°F
-29°C
-20°F
Heat of Rejection
Air Conditioning
4600
3800
5400
6100
5400
9000
13900
13000
16000
13000
16000
16250
18600
20700
24500
23500
27000
31000
36000
45000
51000
43°C
110°F
49°C
120°F
49°C
120°F
54°C
130°F
Peak
5450
6000
6300
6900
6300
9