Pressure Sensor
72
Curve
73
Multiplex Input 1
74
Level Sensor Curve
75
Multiplex Input 2
76
Config. Sensor Curve (0-9) (0-9) (0-5)
77
Poles
78
Temp. Sensor Open
79
OP Sensor Open
Fuel Level Sen-sor
80
Open
81
Config. Sensor Open
82
Cooling Blower On
83
Cooling Blower Off
84
Low Fuel Level Warn
85
Gen Over Volt Warn
86
Gen Under Volt
87
Gen Over Freq Warn
Gen Under Freq
88
Warn
Gen Over Current
89
Warn
90
High Temp. Warn
91
Low OP Warn
92
Aux. Sensor Warn
HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
(0-12)
8
(0-1)
0
(0-7)
3
(0-3)
0
8 8 3
(2-64)
4
(0-2)
1
(0-2)
1
(0-2)
1
(0-2)
1
(0-140)ºC
60
(0-140)ºC
40
(0-100)%
20
(30-620)V
253
(30-620)V
193
(0-75.0)Hz
55.0
(0-75.0)Hz
42.0
(50-130)%
110
(80-140)ºC
95
(0-400)kPa
124
(80-140)ºC (0-400)kPa
95
(0-100)%
SGX See 7.4
0: Digital Input 3
1: Level Sensor
SGD See 7.4
0: Digital Input 4 1: Temperature Sensor 2: Oil
Pressure Sensor 3: Level Sensor Note 5
SGX SGX SGD
0:Defined temperature sensor
1: Defined pressure sensor
2: Defined liquid level sensor
Select the sensor, input corresponding 8 values.
0:Indication; 1:Warn; 2:Shutdown (temperature
sensor will show "+++");
0: Indication (oil pressure sensor will show "+++");
1:Warn; 2:Shutdown
0: Indication (fuel level sensor will show "+++");
1:Warn; 2:Shutdown
0: Indication (LCD display will show "+++");
1:Warn; 2:Shutdown
It controls the cooling blower to open or close if
the output port is configured as Cooling Blower.
When the liquid level of the exter-nal sensor falls
below the set value, "Low Fuel Level" timer is
initiated. (this only concerns fuel level sensor and
does not concern low fuel level warning signal via
configurable input port)
When genset voltage is over the point, genera-tor
over voltage is active. When the point is 620V,
generator over voltage is disa-bled.
When generator voltage is under the point, genera-
-tor under voltage is active. When the point is 30V,
generator under voltage is disabled.
When generator's frequency is over the point,
genera-tor over frequen-cy is active.
When generator frequency is lo-wer than the point,
warn alarm signal will be sent.
When load cur-rent is over the point, over current
is active. When this value is 0, warn alarm signal
won't be sent.
When the tempe-rature value of the external
tem-perature sensor exceeds the set value, "High
Temperature" timer is initiated. Detecting only after
safety on delay has expired. If the set value is 140,
high tempe-rature signal will not be sent (this only
concerns external tempera-ture sensor, not high
temperature signal via config. input port).
When the exter-nal pressure sen-sor value falls
below this set value, "Low Oil Pressure" timer
is initiated. Detec-ting only after safety on delay
has expired. If the set value is 0, low oil pressure
signal will not be sent (this only con-cerns pressu-
re sensor and does not concern low oil pressure
war-ning signal via configurable input port)
Respective cor-responding with 90 temp. sensor,
91 pressure sen-sor and 84 level sensor in this
table.
10