4.DEFINITION AND RANGE OF PARAMETERS
No.
Items
1
Mains Normal Delay
Mains Abnormal
2
Delay
3
Mains Under Volt
4
Mains Over Volt
5
Transfer Rest Delay
6
Start Delay
7
Stop Delay
8
Start Attempts
9
Preheat Time
10
Cranking Time
11
Crank Rest Time
12
Safety On Delay
13
Start Idle Time
14
Warming Up Time
15
Cooling Time
16
Stop Idle
17
ETS Solenoid Hold
18
Fail to Stop Delay
19
Breaker Close Time
20
Flywheel Teeth
21
Gen Abnormal Delay
22
Gen Over Volt
HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
Range
Default
(0-3600)s
10
(0-3600)s
5
(30-620)V
184
(30-620)V
276
(0-99.9)s
1.0
(0-3600)s
1
(0-3600)s
1
(1-10)times
3
(0-300)s
0
(3-60)s
8
(3-60)s
10
(1-60)s
10
(0-3600)s
0
(0-3600)s
10
(3-3600)s
10
(0-3600)s
0
(0-120)s
20
(0-120)s
0
(0-10)s
5.0
(10-300)
118
(0-20.0)s
10.0
(30-620)V
276
Description
The time from mains abnormal to normal or
from normal to abnormal; suitable for ATS (auto-
matic transfer switch).
When mains voltage has fallen below the set value,
Mains Under Voltage is active. When set the value
as 30V, the controller does not detect under volta-
ge signal. Back lash: 10V
When mains voltage has exceeded the set value,
Mains Over Voltage is active. When set the value
as 620V, the controller does not detect over volta-
ge signal. Back lash: 10V
Interval time from mains switch off to generator
switch on; or from generator switch off to mains
switch on.
Time from mains abnormal or remote start signal
is active to start genset.
Time from mains normal or remote start signal is
deactivated to genset stop.
Maximum crank times of crank attempts. When
reach this number, controller will send start failure
signal.
Power-on time of heater plug before starter is
powered up.
Power-on time of starter
The waiting time before second power up when
engine start fail.
Alarms for low oil pressure, high temperature,
under speed, under frequency/voltage, charge alt
failure are inactive.
Idle running time of genset when starting.
Warming time between genset switch on and high
speed running.
Radiating time before genset stop, after it unloads.
Idle running time when genset stop.
Stop electromagnet's power on time when genset
is stopping.
Time between ending of genset idle delay and
stopped when "ETS time" is set as 0;
Time between ending of ETS hold delay and
stopped when "ETS time" is not 0.
Pulse width of mains/generator switch on. When it
is 0, means output constantly.
Tooth number of the engine, for judging of starter
crank disconnect conditions and inspecting of
engine speed. See the installation instructions.
The alarm delay of generator over voltage and
under voltage.
When generator voltage has exceeded the set
value and the "Gen abnormal delay" has expired,
Gen Over Voltage is active. When set the value as
620V, the controller does not detect over voltage
signal.